D&W psiioSYSTEM x²
Description
Steuern Sie Ihre Wärmepumpe von drexel und weiss via RS232
Inputs and outputs · 31
| Name | Type | Command | Unit |
|---|---|---|---|
| Outside air temperature | Comm | LU 202 \v | °C |
| CO2 | Comm | LU 230 \v | ppm |
| Fan speed exhaust | Comm | LU 1186 \v | 1/min |
| Fan speed supply | Comm | LU 1184 \v | 1/min |
| Change fine particle filter | Comm | LU 7004 \v | <v> |
| Change coarse particle filter | Comm | LU 7002 \v | <v> |
| Error 1 (LU) | Comm | LU 800 \v | |
| Error 2 (LU) | Comm | LU 7500 \v | |
| Room temperature | Comm | WP 200 \v | °C |
| Temperature solar panel | Comm | WP 242 \v | °C |
| Floor temperature | Comm | WP 216 \v | °C |
| Error 1 (WP) | Comm | WP 800 \v | |
| Error 2 (WP) | Comm | WP 7500 \v | |
| Boiler temperature (EHZ) | Comm | WP 212 \v | °C |
| Mode_WLG | Comm | LU 5002 \v | <v> |
| Water set temperature (psiio) | Comm | WP 5064 \v | °C |
| Room set temperature (psiio) | Comm | WP 5016 \v | °C |
| Boiler temperature (solar) | Comm | WP 244 \v | °C |
| Flow low-temperature heating circuit | Comm | WP 240 \v | °C |
| Requirement: passive cooling | Comm | WP 1142 \v | |
| Boiler temperature (heat pump) | Comm | WP 214 \v | °C |
| Fan level 1 | Comm | LU 5002 1\n\r | |
| Fan level 2 | Comm | LU 5002 2\n\r | |
| Fan level 3 | Comm | LU 5002 3\n\r | |
| Fan Automatic | Comm | LU 5002 4\n\rLU 1048 1\n\r | |
| Party | Comm | LU 5002 5\n\r | |
| Fan off | Comm | LU 5002 0\n\r | |
| Function bathroom + | Comm | WP 5036 1\n\r | |
| Function heating + | Comm | WP 5492 1\n\r | |
| Room set temperature | Comm | WP 5016 <v.1>\n\r | °C |
| Water set temperature | Comm | WP 5064 <v>\n\r | °C |