Image of Nibe (KNV) Heating & Cooling (S-Series)
Template

Nibe (KNV) Heating & Cooling (S-Series)

by KNV Energietechnik GmbHBrand: KNVNo rating yet1,124 downloads

Content languageEnglish

Description

This template allows you to control your Nibe Heatpump "S-Series" direct without Gateway over Modbus TCP. The Nibe "SMO S40" is the control system for Air/Water, Brine/Water, Water/Water Heatpumps from Nibe. The "F series" with "SMO 40" of Nibe is a type of older system and can therefore only be integrated as a slave participant. You can find the template in the following link : Nibe F-Series The datapoints between the F-series, S-series and Greenline from Nibe (KNV) differ significantly.


The choice of paring Nibe Heatpumps with Loxone offers the possibility of:

- integrating demand-based heating and cooling depending on e.g. presence or the protection of open windows - Interaction with the blinds for saving effects by passive cooling thanks to Loxone automatic shading - Active integration in interaction with e.g. PV- systems in a Loxone Energy Management - Using flexible electricity tariffs with the Spot Price Optimizer. - Use statistics ore individual notifications - Create your own individual schematics - Reduce cycles and operating hours of your Nibe Heatpump - Create e.g. yearly operation goals like certain annual runtime forces for hybrid systems e.g. (Heatpump 60% amount of energy, Gas heater 40% amount of energy) to fulfill the requirements of your local government. - Grid management according to §14a ENWG in Germany - In addition to the electrical power, the current and total thermal energy can also be visualized via the Loxone Energy Flow Monitor. To the compact overview for e.g. contractors. - Influence on the hot water circulation pump by controlling via the presence detectors. - Increased security through leakage detection or activation of IP cameras in the plant room.

With our step by step manual for collecting the heating or cooling demand and forwarding it to the Nibe heatpump, we enable the interaction of the individual room control with the central heating/cooling system of Nibe. Please take a look on the Loxone Config sample file in the Library download area.

If you need a full list of all Modbus registerts, insert a USB-stick into the USB port of the HMI. Navigate to menu 7.5.9 Modbus TCP/IP and select "Export most used registers" or "Export all registers". This creates a full list of modbus registers in a .csv file.


Structure:

Please note: The LAN cable is connected to the controller for the air/water heat pump and to the Touch control module for the brine/water heat pump


Nibe helpcenter and download area:

- If you need help how to deal with the integration of the "SMO S 40" operation system or need general information, please use the multilingual Nibe homepage. Unfortunately, Nibe does not have all documents in their download area. Therefore, the documentation in our download area must always be checked for the latest version with the partner or seller for completeness and functionality. - In some countries it is possible to access the manual download area. e.g. for German:

Activation of Modbus: Activation of external heating/cooling request:


UseCase: Integration of a Nibe Topline S1156: Commercial building with heating, cooling, heat buffer, warm water storage and heating circuit.

- Device Brine/Water Topline S1156 - Heating/Cooling buffer tank - Warm water storage tank --> Controlled by Loxone - Mixing circuit heating/cooling HC1 (e.g. ceiling heating/cooling) --> Controlled by Loxone

Functional Components required for Loxone Integration in the example schematic:

Inputs and outputs · 48

NameTypeUnit
Actual Outdoor temperature [BT1]Modbus°C
Actual Hot Water Bottom temperature [BT6]Modbus°C
Acutal Supply Flowtemperature HC1 [BT2]Modbus°C
State Room temperature HC1 [BT50]Modbus°C
State Offset Curve HC1Modbus<v.1>
State Heat Curve HC1 [BT50]Modbus<v.0>
Total Thermal Power HeatingModbuskWh
Total Operating time direct heaterModbush
Actual Return temperature HC1 [BT3]Modbus°C
Actual Brine Out Flowtemperature [BT11]Modbus°C
Actual Brine In Flowtemperature [BT10]Modbus°C
State CompressorModbus<v.0>
Actual Hot Water Top temperature [BT7]Modbus°C
Total Thermal Power Hot WaterModbuskWh
Actual Heatpump Flowtemperature [BT12]Modbus°C
Actual Liquid Line temperature [BT15]Modbus°C
Actual Outdoortemperature [BT1]Modbus°C
Actual Heatpump Flow Sensor [BF1]Modbusl/m
State Brine Pump Speed [GP2]Modbus%
State Compressor StartsModbus<v>
State Circulation pump HC1 [GP10]Modbus%
State Calculated Supply FlowtemperatureModbus°C
Actual Electrical Power CompressorModbusW
State Compressor Operation hoursModbush
State Hot Water DemandModbus<v.1>
State Hot Water operation modeModbus<v>
State Cooling operation modeModbus<v.1>
State Heatpump Operating prioritisationModbus<v.1>
Actual Flowtemperature Buffer to HC [BT25]Modbus°C
State Circulationpump HC1Modbus<v>
Actual Current BE3ModbusA
Actual Current BE2ModbusA
Actual Current BE1Modbus<v.1>
State Heatpump Operating modeModbus<v.1>
Actual Electrical PowerModbusW
State Hot Water Circulation pump [GP11]Modbus<v.1>
State Target Heating Supply Flowtemperature HC1Modbus°C
State Target Cooling Supply Flowtemperature HC1Modbus°C
State Alarm numberModbus<v>
State Active alarmModbus<v>
Heating Curve Offset HC1Modbus<v.1>
Heating Curve HC1Modbus<v.1>
Hot Water DemandModbus<v.1>
Target Heating Supply Flowtemperature HC1Modbus°C
Target Cooling Supply Flowtemperature HC1Modbus°C
Operation mode HeatpumpModbus<v>
Release Heating at manual modeModbus<v.1>
Release Cooling at manual modeModbus<v>

FAQ

No questions have been answered yet.

Ratings and comments

No ratings or comments yet.

Questions and answers

  1. Hot Water Circulation

    Open

    Hi,

    I've been using this for HW demand control linked to energy and wanted to try and control the HW Circulation Pump (GP11). How is this achieved? I've created an AQ with what i thought was the correct register however this doesn't seem to be working.

    I note that you say it can influence hot water circulation pump by controlling via the presence detectors - do you have an example of this or am i missing something. Heatpump is Nibe S1155.

    Thanks

    No replies

  2. Can I use this modbus template with NIBE S320?

    Open

    Hi there, our customer own heat pump Nibe VVM S320. We need to connect with Loxone via Modbus TCP/IP. Modbus template is not included in supported devices. Can we use it for NIBE S320 or it is not recomended please? Thank you

    1 reply

    1. Hi, I am sorry for the late reply. I may had no notification about the your question.

      Your customer can use the template as VVM S320 is part of the S-Series.

  3. Open

    funktioniert das Teamplate auch mit der Wärmepumpe alira NP-AW 20 Serie und dem Regler NP-CS 40 ?

    1 reply

    1. Guten Tag, für den NP-CS 40 ist das Template der F-Series zu verwenden: https://library.loxone.com/detail/nibe-fserial-1574/overview Der NP-CS 40 entspricht dem SMO 40

  4. Gibt es ein Template für KNV S320 + S2125?

    Open

    Liebes KNV/NIBE Team,

    Habt ihr ein Template für die Kombination KNV S320 + S2125? Könntet ihr es als Anhang an dieses Template anfügen? Oder zumindest eine kleine Checkliste was mit dieser Hardware steuerbar ist?

    Beste Grüße Christopher

    2 replies

    1. Hallo Christopher,

      das (KNV) VVM S320 ist Teil des S-Reglers. Im Wesentlichen sind alle Geräte mit S-Regler gleich aufgebaut. Falls eine Liste mit verwendeten Modbus-Registern erforderlich ist, kann diese direkt am Gerät erstellt werden. Einfach einen USB-Stick mit max. 16 GB einstecken, ins Modbus Menü navigieren und den Button "Register exportieren" nutzen. In dieser Liste sind alle Register aufgeführt, inklusive Registergröße, Type, Divisionsfaktor. Ein konkretes Template für VVM S320 und S2125 gibt es nicht.

      Beste Grüße Alexander Wagner

    2. Hallo Christopher,

      das (KNV) VVM S320 ist Teil des S-Reglers. Im Wesentlichen sind alle Geräte mit S-Regler gleich aufgebaut. Falls eine Liste mit verwendeten Modbus-Registern erforderlich ist, kann diese direkt am Gerät erstellt werden. Einfach einen USB-Stick mit max. 16 GB einstecken, ins Modbus Menü navigieren und den Button "Register exportieren" nutzen. In dieser Liste sind alle Register aufgeführt, inklusive Registergröße, Type, Divisionsfaktor. Ein konkretes Template für VVM S320 und S2125 gibt es nicht.

      Beste Grüße Alexander Wagner

  5. SMO S40 + 2xS2125-16

    Open

    Hallo Zusammen,

    ich habe die Kombination SMO S40 + 2xS2125-16 verbaut. Via dem Template erhalte ich einen Großteil der Werte, jedoch aber keine Strom Verbrauchswerte für den Energiemaanger "Actual Electrical Power" hat ein rotes Ausrufezeichen und bleibt leer. Ich habe das System bereits via Modus mit meinem Fronius Wechselrichter verbunden um hier Überschussenergie zu nutzen. Wird der Wert ggf. nur einmal übergeben? Danke für Input! Martin Kaminski

    2 replies

    1. Guten Tag Herr Kaminski,

      bei dem Template handelt es sich um ein allgemeines Template. Die momentan verwendete Leistung ist ein Parameter, welcher bei Erdwärmepumpen der S1x55 und S1x56 Serien angezeigt wird. In der aktuellen Software 4.11.5 für den SMO S40 gibt es das Modbusregister mit der Nummer 2305 mit dem Titel "Energieprotokoll - Tatsächlicher Energieverbrauch" im Format u32 mit dem Divisionsfaktor 100 in der Einheit kW. Liest man dieses Register bspw. mit Modbus Poll aus, so muss man beim Format folgendes wählen: 32-bit Unsigned, Little-endian byte swap. D.h. in Loxone müssten Sie für den Energieverbrauch des Systems das oben genannte Modbus Register verwenden.

      Sie können immer die aktuelle Registerliste direkt am SMO S40 exportieren. Schließen Sie dazu einen USB Stick mit max. 16 GB am Gerät an, navigieren Sie ins Menü 7.5.9 und tippen Sie auf "Alle Register exportieren". Damit erhalten Sie die vollständige, aktuell gültige Modbus Registerliste.

      Beste Grüße Alexander Wagner

    2. Danke Herr Wagner, leider konnte ich das komplette Register nicht runterladen, habe zwei Stick probiert, beide unter 16GB in FAT 32. Gibt es da alternativ noch einen Trick? Ich werde das ganze dann nach meinem Urlaub in 2 Wochen probieren.

      Viele Grüße Martin Kaminski

Report this entry

Report abuse

You have to be logged in to report an entry. Log in