Description

A Nibe (KNV) heatpump is a Nibe heat pump for the Austrian market. The devices do not differ technically, only in their name. The Nibe (KNV) F series is an older Heatpump model series and can be integrated into Loxone with a Modbus 40 gateway.

The Nibe (KNV) S-series is the new Heatpump model series and is listed in a different template. There are two different ways how to connect Nibe F-Series with Loxone:

- Nibe Modbus 40 RTU Gateway with Loxone Modbus Extension - Nibe Modbus 40 RTU Gateway with a Loxone Modbus Air.

Modbus TCP is not supported! The datapoints between the F-series, S-series and Greenline from Nibe (KNV) differ significantly.


The choice of paring Nibe Systems with Loxone offers the possibility of:

- Integrating demand-based heating and cooling depending on e.g. presence or the protection of open windows - Active integration in interaction with e.g. PV- systems in a Loxone Energy Management - Using flexible electricity tariffs with the Spot Price Optimizer. - Use statistics ore individual notifications - Create your own individual schematics - Reduce cycles and operating hours of your Nibe Heatpump - Combining hybrid solutions e.g. Nibe Heatpump and PV- Heating element in your Hot Water Storage - Create e.g. yearly operation goals like certain annual runtime forces for hybrid systems e.g. (F1145 -->60% amount of energy, Gasboiler --> 40% amount of energy) to fulfill the requirements of your local government.

With our step by step manual for collecting the heating or cooling demand and forwarding it to the Nibe heatpump, we enable the interaction of the individual room control with the central heating/cooling system of Nibe. Please take a look on the Loxone Config sample file in the Library download area.


Structure:


Nibe (KNV) helpcenter/download area/commissioning:

- You can find the Modbus 40 Gateway Manual below or the latest version at the document search. Choose your language, all accessories at the product group and modbus 40 at the product list. - If you need help how to deal with the integration of the "Modbus 40 Gateway" operation system or need general information, please use the multilingual Nibe homepage. Unfortunately, Nibe does not have all documents in their download area. Therefore, the documentation in our download area must always be checked for the latest version with the partner or seller for completeness and functionality. - The Nibe Modbus manager is required for Modbus communication with the Modbus 40 Gateway and 20 data points must be defined in advance. An explanation of how to use the Modbus manager can be found in the Modbus 40 manual.The parameter set is transferred to the Nibe heat pump control unit via a USB stick. - You can find the Modbus addresses and parameters for your F-Serial on OpenHab. For the F-Series 1145 for example in the following Link.

Example of the download area:

Inputs and outputs · 27

NameTypeUnit
40004 Actual OutdoortemperatureModbus°C
40014 Actual Hot Water TemperatureModbus°C
45001 State Alarm CodeModbus<v>
47041 State Hot Water OperationmodeModbus<v.0>
40008 Actual Supply Flow TemperatureModbus°C
40033 Actual RoomtemperatureModbus°C
47011 State Roomtemperature OffsetModbus<v.1>
47007 State HeatingcurveModbus<v.0>
40012 Actual Back Flow TemperatureModbus°C
40016 Actual Brine Out TemperatureModbus°C
40015 Actual Brine In TemperatureModbus°C
43427 State CompressorModbus<v.0>
43005 Degree MinutesModbusMin
43086 Actual Heatpump OperationmodeModbus<v>
42100 Actual Outdoortemperature average (24h)Modbus°C
47398 State Roomsensor SetpointModbus°C
47402 State Roomsensor Factor SetpointModbus<v>
47371 State Heating ReleaseModbus<v.1>
47394 State RoomsensorModbus<v>
47041 Hot Water Operation modeModbus<v>
47011 Heating Curve OffsetModbus<v>
47007 Heating CurveModbus<v>
44243 Operation ModeModbus<v>
47398 Roomtemperature SetpointModbus<v>
47402 Room Sensor Factor SetpointModbus<v>
47371 Release HeatingModbus<v>
47394 Room Sensor Operation modeModbus<v>

FAQ

No questions have been answered yet.

Ratings and comments

No ratings or comments yet.

Questions and answers

  1. modbus nibe f1255 pc

    Open

    the modbus module of loxone has been connected with three wires B/GROUND/A

    the f1255 are connected on 9-ground/10-a/11-b on the installation guide provided via loxone of nibe connection point 12 is indicated that it should be connected with 12V.

    up till now cannot make connection with the nibe via the loxone modbus // which step can I take

    No replies

  2. modbus nibe f1255 pc

    Open

    the modbus module of loxone has been connected with three wires B/GROUND/A

    the f1255 are connected on 9-ground/10-a/11-b on the installation guide provided via loxone of nibe connection point 12 is indicated that it should be connected with 12V.

    up till now cannot make connection with the nibe via the loxone modbus // which step can I take

    1 reply

    1. Hello Hendrik,

      it looks like you have mismatched the connections. It need to be 10-B and 11-A.

      More details:

      Have you connected the Modbus40 module according to the installer handbook with the heat pump? https://professional.nibe.eu/document/Installer%20manual%20(IHB)/031725-10.pdf The connections of the Modbus 40 (AA9-X1) need to be connected to AA3-X4 on the heat pump. --> AA9-X1 12V to AA3-X4 12 --> AA9-X1 A to AA3-X4 11 --> AA9-X1 B to AA3-X4 10 --> AA9-X1 GND to AA3-X4 9

      The Loxone module needs to be connected to Modbus40 (AA9-X2). Please don't forget the 120 Ohm termination resistor, see Screenshot in the Library.

  3. modbus

    Open

    overview " - You can find the Modbus 40 Gateway Manual always up to date in the following link: Modbus 40 Gateway // this link doesn't function any more on your website

    - The Nibe Modbus manager is required for Modbus communication with the Modbus 40 Gateway and 20 data points must be defined in advance. An explanation of how to use the Modbus manager can be found on pages 20-22.The parameter set is transferred to the Nibe heat pump control unit via a USB stick. // this link doesn't function anymore

    can you send me the 20 parameters that i need to download in the modbus manager

    1 reply

    1. You can find the link to the Modbus 40 manual in my last reply and now also in the library.

      Choose the 20 paramaters which you need. Please find the registerst at OpenHab

  4. modbus nibe heatpump

    Open

    I can only adjust via settings modbus in loxone -baudrate -stopbits -parity -timing

    although in the official link of nibe; i should be able to able change around 20 modbus settings (link is also website loxone) which are devided in four categories: communication; timing; frame and data

    1 reply

    1. Hello Hendrik,

      please reply to my answers instead of opening a new thread for every message.

      Read carefully the manual of the Modbus 40. You can choose 20 variables which should be read or written with your loxone system. Therefore you need the program "modbus manager" which is downloadable at the template webpage. Nowhere is written that you can change 20 settings. After choosing the variables you can transfer them as a "LOG.SET" file onto a USB stick which then needs to be connected to your heat pump. On the heat pump you need to activate the protocol.

Report this entry