M-TEC Heating & Cooling
Description
Control your M-TEC Heating & Cooling System via Modbus TCP. M-TEC with the [ZP022] Operating system can be directly connected to Loxone without a Gateway.
Depending on variation of your project you can choose between Miniserver, Miniserver Go or Miniserver Compact M-Tec also has its own PV management system with his own battery storage. The integration is shown in a separate template: M-TEC Energy Butler.
The Choice of paring M-TEC Systems with Loxone offers the possibility of:
- Integrating demand-based heating and cooling depending on e.g. presence or the protection of open windows, Automatic Shading and Weatherforecast. - Active integration in interaction with e.g. PV- systems in a Loxone Energy Management - Load management in areas where the building's electricity connection is low - Using flexible electricity tariffs with the Spot Price Optimizer. - Use statistics or individual notifications - Create individual live system schematics. - Reduce cycles and operating hours of your M-TEC Heatpump or Subdevices. - Combining hybrid solutions e.g. Heatpump and PV- Heating element in your Hot Water Storage - Create e.g. yearly operation goals like certain annual runtime forces for hybrid systems e.g. (Belaria 60% amount of energy, UltraGas 40% amount of energy) to fulfill the requirements of your local government. - Grid management according to §14a ENWG in Germany - Blackoutsafe! Switch off the Heatpump if the Grid power fails e.g. emergency power is active to safe battery capacity. - Use the flexible ways of reading thermal heat meters and electricity meters via e.g. M-Bus or IR readers and the thermal or electrical visualization in the Loxone Energy Flow Monitor. For e.g. Contractors. - Whether residential or commercial buildings. No matter whether M-TEC or Loxone is the main operator, no matter which hydraulics and consumers. Connecting M-TEC Heatpumps with Loxone systems allows the demand-oriented and intelligent distribution of energy thanks to distribution solutions from Belimo or IMI TA. - Influence on the hot water circulation pump by controlling via the presence detectors. - Increased security through leakage detection or activation of IP cameras in the plant room. - Use of the Heatpump to operate a Pool and to automatically control the switching of heating, cooling and hot water. - Connectivity and setup of heating centers and heating substations with the flexible ways of Loxone intercommunication.
M-TEC Helpcenter, download area and activation of Modbus:
- If you need help with e.g. the configuration of Modbus within the M-TEC operation unit please contact your M-TEC Partner. The Partner or the M-TEC customer service can be commissioned for this purpose. - To activate Modbus TCP on the M-TEC unit, please take a look on the following video, please note that the modbusadress is always "1". The Networksettings have to be common with the Loxone Config Settings on the Modbusserver.
Example UseCase: Integration M-TEC Brine System: Residential building with Heatpump, Hot Water storage, Heating/Cooling Buffer and Heating/Cooling circuits.
- [A1] Device Brine/Water e.g. M-TEC WPS - [A2] Passive Cooling with Ground Probe (Brine) - [A3] Heating/Cooling Buffer - [A4] Hot Water Storage Tank --> Controlled by Loxone - [A5] Fresh Water System - [HC1] Mixing Circuit Heating/Cooling HC1 (e.g. Ceiling Basement) --> Controlled by Loxone - [HC2] Mixing Circuit Heating/Cooling HC2 (e.g. Ceiling Groundfloor) --> Controlled by Loxone - [HC3] Mixing Circuit Heating/Cooling HC3 (e.g. Fancoils Office) --> Controlled by Loxone
With our step by step manual for collecting the Heating or Cooling Demand and forwarding it to the M-TEC WPS, we enable the interaction of the individual room control with the Central Heating & Cooling System of M-TEC. Please take a look on the Loxone Config sample file in the Library download area.
Inputs and outputs · 71
| Name | Type | Unit |
|---|---|---|
| State Heatpump Operating Hours | Modbus | h |
| Actual Outsidetemperature | Modbus | °C |
| State Hot Water Operatingmode | Modbus | <v> |
| Actual Hot Water temperature | Modbus | °C |
| State Target Roomtemperature HC1 | Modbus | °C |
| Actual Operating mode HC1 | Modbus | <v> |
| Actual Room Humidity HC1 | Modbus | % |
| Actual Roomtemperature HC1 | Modbus | °C |
| Actual Electrical Heatpump Power | Modbus | W |
| Actual Heatpump Thermal Power | Modbus | kW |
| State Heatpump Operationmode | Modbus | <v> |
| State Heatpump Total Electrical Energy | Modbus | kWh |
| Actual Operating mode HC2 | Modbus | <v> |
| Actual Operating mode HC3 | Modbus | <v> |
| Actual Room Humidity HC2 | Modbus | % |
| Actual Room Humidity HC3 | Modbus | % |
| Actual Roomtemperature HC2 | Modbus | °C |
| Actual Roomtemperature HC3 | Modbus | °C |
| State Target Roomtemperature HC2 | Modbus | °C |
| State Target Roomtemperature HC3 | Modbus | °C |
| State Heatpump Error | Modbus | <v> |
| State Target Supplyflowtemperature HC1 | Modbus | °C |
| Actual Supplyflowtemperature HC1 | Modbus | °C |
| Actual Supplyflowtemperature HC2 | Modbus | °C |
| Actual Supplyflowtemperature HC3 | Modbus | °C |
| State Target Supplyflowtemperature HC2 | Modbus | °C |
| State Target Supplyflowtemperature HC3 | Modbus | °C |
| Actual Hot Water Targettemperature | Modbus | °C |
| Actual Buffertemperature Top | Modbus | °C |
| State Heatpump operation state | Modbus | <v> |
| Actual Heatpump Supplyflowtemperature | Modbus | °C |
| Actual Heatpump Backflowtemperature | Modbus | °C |
| Actual Heatpump Brine IN Temperature | Modbus | °C |
| Actual Heatpump BrineOUT Temperature | Modbus | °C |
| State Heatpump Targetttemperature | Modbus | °C |
| State Compressorspeed | Modbus | % |
| State Coolrequest Buffer | Modbus | <v> |
| State Coolrequest HC1 | Modbus | <v> |
| State Coolrequest HC2 | Modbus | <v> |
| State Coolrequest HC3 | Modbus | <v> |
| State Heatrequest Buffer | Modbus | <v> |
| State Heatrequest HC1 | Modbus | <v> |
| State Heatrequest HC2 | Modbus | <v> |
| State Heatrequest HC3 | Modbus | <v> |
| Actual Buffertemperature Bottom | Modbus | °C |
| HC. 1 normal room temperature | Modbus | °C |
| Set System Operation mode | Modbus | <v> |
| HC. 1 offset room temperature | Modbus | K |
| Set Operationmode HC1 | Modbus | <v> |
| Set cooling requirement HC1 | Modbus | <v> |
| Set heating requirement HC1 | Modbus | <v> |
| Set Target Supplyflowtemperature HC1 | Modbus | °C |
| Set Hot Water Targettemperature | Modbus | °C |
| HC. 1 lower room temperature | Modbus | °C |
| Set Outside temperature | Modbus | °C |
| PV. current surplus power | Modbus | kW |
| Set Hot Water Operationmode | Modbus | <v> |
| HC. 2 lower room temperature | Modbus | °C |
| HC. 3 lower room temperature | Modbus | °C |
| Set Operationmode HC2 | Modbus | <v> |
| Set Operationmode HC3 | Modbus | <v> |
| Set heating requirement HC2 | Modbus | <v> |
| Set heating requirement HC3 | Modbus | <v> |
| Set cooling requirement HC2 | Modbus | <v> |
| Set cooling requirement HC3 | Modbus | <v> |
| HC. 2 normal room temperature | Modbus | °C |
| HC. 3 normal room temperature | Modbus | °C |
| HC. 2 offset room temperature | Modbus | K |
| HC. 3 offset room temperature | Modbus | K |
| Set Target Supplyflowtemperature HC2 | Modbus | °C |
| Set Target Supplyflowtemperature HC3 | Modbus | °C |
FAQ
No questions have been answered yet.
Questions and answers
Blackoutsafe!
OpenLiebes M-TEC Loxone Team. Wie lässt sich die Wärmepumpe wie in der BEschreibung angeführt (Blackoutsafe) kontrolliert herunterfahren? Welche Aktor kann für das verwendet werden? Danke für die Hilfe mfg
No replies
Log in to rate, comment or ask a question. Log in
Ratings and comments
No ratings or comments yet.
Log in to rate, comment or ask a question. Log in