Inputs and outputs · 26

NameTypeCommandUnit
AussenlufttemperaturCommLU 202 \v°C
CO2CommLU 230 \vppm
Drehzahl AbluftventilatorCommLU 1186 \v1/min
Drehzahl ZuluftventilatorCommLU 1184 \v1/min
Feinstaubfilter wechselnCommLU 7004 \v<v>
Grobstaubfilter wechselnCommLU 7002 \v<v>
Summenstörung 1 (LU)CommLU 800 \v
Summenstörung 2 (LU)CommLU 7500 \v
RaumtemperaturCommWP 200 \v°C
Summenstörung 1 (WP)CommWP 800 \v
Summenstörung 2 (WP)CommWP 7500 \v
Temp. Boiler (EHZ)CommWP 212 \v°C
Modus_WLGCommLU 5002 \v<v>
Brauchw. Soll-Temp. (psiio)CommWP 5064 \v°C
Raum Soll-Temp. (psiio)CommWP 5016 \v°C
Temp. Boiler (Wärmepumpe)CommWP 214 \v°C
Ventilator Stufe 1CommLU 5002 1\n\r
Ventilator Stufe 2CommLU 5002 2\n\r
Ventilator Stufe 3CommLU 5002 3\n\r
Ventilator AutomatikCommLU 5002 4\n\rLU 1048 1\n\r
PartyCommLU 5002 5\n\r
Ventilator AusCommLU 5002 0\n\r
Raum Soll-TemperaturCommWP 5016 <v.1>\n\r°C
Brauchwasser Soll-TemperaturCommWP 5064 <v>\n\r°C
Funktion BAD +CommWP 5036 1\n\r
Funktion HEIZUNG +CommWP 5492 1\n\r

FAQ

No questions have been answered yet.

Ratings and comments

No ratings or comments yet.

Questions and answers

  1. Correct RS232 Interface Settings for Drexel & Weiss Aerosmart

    Open

    Dear Loxone Support Team,

    I am currently trying to re-establish communication between my Loxone system and a Drexel & Weiss Aerosmart unit via the RS232 interface.

    The communication was previously working without any issues. However, after reinstalling/replacing the RS232 adapter, the connection is no longer functioning correctly. I am now only receiving unreadable or junk data from the Aerosmart controller.

    Could you please advise what the correct RS232 communication settings should be (baud rate, parity, data bits, stop bits, flow control, etc.) to ensure proper communication with the Drexel & Weiss Aerosmart?

    Additionally, are there any specific configuration steps required in Loxone after reinstalling the adapter that I should be aware of?

    Thank you in advance for your support.

    Best regards, Walter