Inputs and outputs · 14

NameTypeUnit
Total Output EnergyModbuskWh
Total DC powerModbuskW
Total PV GenerationModbuskWh
Total Export Energy from PVModbuskWh
Total direct energy consumptionModbuskWh
Battery powerModbuskW
Battery state of healthyModbus%
Self-consumption of today in percentModbus%
Total active powerModbuskW
Total Import EnergyModbuskWh
Total Export EnergyModbuskWh
Battery levelModbus%
Running stateModbus<v.1>
Export PowerModbuskW

FAQ

No questions have been answered yet.

Ratings and comments

No ratings or comments yet.

Questions and answers

  1. Example is wrong

    Open

    We use IO 13021 on Spwr. This is an unsigned integer. Battery is always discharging. IO 13000 gives charging/discharging (Appendix 1.2), use a Binary Decoder. Feel free to contact me or Christoph Pfoser.

    No replies

  2. Battery power

    Open

    der wert kommt nu als positiver wert. wie kann ich erkennen ob die batterie lädt oder entlädt?

    1 reply

    1. wenn das stimmt, was hier und im Sungrow Dokument steht, dann musst du den Running State mit einem Binärdekoder verknüpfen, das 2. Bit auslesen (steht für charging, oder das 3. Bit für disharging), mit -2 (o. +2) multiplizieren, +1 addieren (o. substrahieren). Das ergibt dir dann eine -1 für den Fall wenn die Batterie geladen wird und +1 für alle andere Fälle. Diesen Wert multiplizierst du mit Battery Power.

  3. Battery Power

    Open

    Warum kann man nicht einfach die Vorlage anpassen? Wichtig ist auch zu wissen, dass man den IO13000 nur über die 2. Buchse vom WR bekommt. Könnte man in die Anleitung packen und somit Supportkraft einsparen....

    3 replies

    1. was heißt das, die 2. Buchse??? Ich habe einen Ethernet Dongle dran.

    2. Hinter dem Dongle ist noch eine Schnittstelle

    3. in der Tat, die "normale" LAN Schnittstelle. Aber die ist nur für TCP Modbus, man muss danach noch immer den Inverter über den Dongle (WIFI oder LAN) mit dem Internet verbinden um die Verbindung zu isolarcloud herzustellen. Wer hat sich denn das überlegt???? Aber jetzt wird dafür der Running State richtig ausgegeben.

  4. IO Adressen um 1 niedriger als im Dokument

    Open

    Soeben wurde der SH10RT in Betrieb genommen.

    Warum sind in dem Template die IO Adressen um 1 niedriger als im Dokument von Sungrow angegeben???? Gibt es schon ein neuers Dokument von Sungrow?

    z.B. "Battery Level" hat im Template eine IO Adresse von 13022 aber im Dokument eine IO Adresse von 13023?!

    Kenn mich nicht aus .....

    Danke für die Hilfe

    2 replies

    1. Hier ein Link zu der Auflistung aller Modbusbefehle mit einer kurzen Erklärung und der tatsächlich zu verwendenden Adressen: https://gist.github.com/dnoegel/543c72ef722365a3934bbad0bb43e222

    2. habe die Antwort auf meine ursprüngliche Frage im Sungrow Dokument selbst gefunden auf Seite 22, gut versteckt:

      Note: Communication address = protocol address – 1. If data of address 5000 is to be inquired, the corresponding sending address data is 4999 (0x1387);

  5. Ppwr configured wrong in "Sungrow Hybrid Example"

    Open

    In my configuration i had to change the Ppwr input. In the example the "Total active power" is connected to Ppwr (this includes also the power from the grid) I had to change it to Total DC power, to see what is produced.

    https://i.imgur.com/AdncNRI.png

    No replies

  6. From Modbus Protocol I can control the discharge et charge par Loxone (modbus)

    Open

    Registre 13050 - EMS mode: 2 (Forced mode) Registre 13051 - Charge/discharge command : =0xAA Charge OU 0xBB Discharge OU 0xCC Stop Registre 13052 - Power : 0-5000W Can you confirme it? Thanks

    No replies

  7. Battarie mit Spot Optimierer

    Open

    Guten Tag Wie kann ich befehle schicken damit Batterie geladen wird weil Strom jetzt günstig von Netz gibt's?? Gibt es ein Modbus Befehl für Batterie??

    No replies

  8. Seit letzem Loxone Update kommen die Werte von Batterie Laden falsch an

    Open

    Hallo Loxone Team, ich habe seit dem letzen Update das Problem das wennd er Akku geladen wird, die Werte vom Modbus falsch ausgegeben werden.Kennt jemand da schon eine Lösung dafür?

    No replies

  9. Sind die neuen SH10T und SH20T sowie SBH kompatibel?

    Open

    Hallo Loxone Team,

    können die neuen Hybrid Wechselrichter SH..T Serien über die Modbus Schnittstelle ausgelesen werden? Gibt es hier aktuelle Adresstabellen?

    1 reply

    1. Dies würde mich auch interessieren, auch in Kombination mit den neuen SBH Speichern wie z.B. SBH250.

  10. SH25T

    Open

    Hi, i've installed the new Sungrow SH25T, does it work with it?

    2 replies

    1. Hello it is not in the supported list so I am unable to confirm this but on the library there is a template for your time of investor available https://library.loxone.com/detail/-923/support; this should work for your device.

    2. i'd like to use Modbus TCP, the other template is for Modbus RTU :-(. but thank you

Report this entry