Template

Spirala heat pump

by Josef StuchlikNo rating yet297 downloads

Content languageEnglish

Description

The Spirala heat pump, hereafter Hp, controls all relevant elements with its electronics, that is, valves, circulation pumps and also issues a signal to start the bivalent source, if needed. It only requires the desired heating water temperature from the superior system and heats the output to this temperature. You will need a Modbus Extension, connect it with a cable to the terminals of the user line of the switchboard module Hp, see Rm.jpg. The terminals are labelled RS485, A, B, gnd, connect them to Modbus Extension terminals of the same name and add 120 Ω termination resistors. In Loxone Config, mark Miniserver, add Modbus Extension, add template "MB_Spirala.xml" and "teach" the extension.

Reading data from Hp. Drag the appropriate Spirala sensor to the page, put a Factor value division behind it, and then a tag. Check "Use in UI" for the tag, set analogue type, units, icon, name and location. The corresponding value will be displayed on the app. To read the status of the fault relay, drag the "Fault relay" sensor, put binary coding behind it, connect output 6 to the digital type mark.

Sending data to Hp. Connect the data source (that is the output of the desired heating water temperature from the Loxone logic) to the x256 multiplication and then to the appropriate Spirala actor.

Important notice. The heating water flow through the heat pump condenser must never be blocked. For circuits without a storage tank, ensure that at least one heating element (radiator) is open. Before closing all heads, the heat pump must be switched off by entering the desired temperature zero. Consider using a storage tank. Consult the manufacturer for solutions. In installations with an accumulation tank, the flow is ensured.

Related documents. Brief description Hp Spirala.pdf Modbus protocol Spirala for Loxone en.pdf Installation example.pdf

Inputs and outputs · 28

NameTypeUnit
DHW tank temperatureModbus°C
Accumulation tank temperature circuit 1Modbus°C
Room temperature 1Modbus°C
Fault relayModbus<v.1>
Accumulation tank temperature circuit 2Modbus°C
Cooling sensor temperatureModbus°C
Outdoor temperatureModbus°C
Room temperature 2Modbus°C
Desired power from PVModbus%
Actual machine powerModbus%
Desired machine power limitationModbus%
Outlet heating water temperatureModbus°C
Return heating water inlet temperatureModbus°C
Primary inlet water temperatureModbus°C
Temperature primary water outletModbus°C
Compressor outlet temperatureModbus°C
Desired temperature of circuit 1Modbus°C
Desired temperature of circuit 2Modbus°C
Desired DHW temperatureModbus°C
Desired room temperature 1Modbus°C
Desired room temperature 2Modbus°C
Desired room temperature 1Modbus°C
Switch the system to coolingModbus
Desired machine power limitationModbus%
Desired temperature of circuit 1Modbus°C
Desired temperature of circuit 2Modbus°C
Desired room temperature 2Modbus°C
Desired DHW temperatureModbus°C