Schneider Energy Meter (3-phase) via Modbus RTU

by LOXONENo rating yet1,024 downloads

Content languageEnglish

Description

This template offers the possibility to read out values from the Schneider energy meter via Modbus RTU.

Inputs and outputs · 24

NameTypeUnit
Product IdentificationModbus<v.0>
Current AModbusA
Current BModbusA
Current CModbusA
Current NModbusA
Voltage A-BModbusV
Voltage B-CModbusV
Voltage C-AModbusV
Voltage A-NModbusV
Voltage B-NModbusV
Voltage C-NModbusV
Active Power AModbuskW
Active Power BModbuskW
Active Power CModbuskW
Active PowerModbusW
Reactive PowerModbusVAR
Apparent PowerModbusVa
FrequencyModbusHz
Energy Active Total ImportModbuskWh
Energy Active Total ExportModbuskWh
Energy Reactive Total ImportModbuskVARh
Energy Reactive Total ExportModbuskVARh
Energy Apparent Total ExportModbuskVAh
Energy Apparent Total ImportModbuskVAh

FAQ

No questions have been answered yet.

Ratings and comments

No ratings or comments yet.

Questions and answers

  1. "Energy Active Total" keine Werte

    Open

    Hallo Zusammen

    Ich habe das Template von Schneider verwendet um folgende Zähler auszulesen. Zähler Typ: REG-Energiezähler Schneider iEM3155 3P+N 63A Modbus Mid

    Ich bekommen alle vordefinierten Werte ausser die folgenden 4: Energy Active Total Import = 20272 Energy Active Total Export = 20270 Energy Reactive Total Import = 20276 Energy Reactive Total Export = 20274

    Können sie mir da weiterhelfen?

    Gruss Stephan

    1 reply

    1. Hello Stephan,

      If you want to read the sate you need to make an input on the modbus template and read the holding register of the same IO address as you are sending to.

      The modbus template is made for a specific device, please keep in mind that when you are using this template with different devices that the modbus addresses may change depending on the product.

      When looking in the added documentation the Energy Active Total Import is on IO address 3203 and not on 20272. This can be the problem you are having.

      Also I see that the device is using 64 bit communication for the total Energy registers. As the iEM3155 is a RTU device it is not possible to read out this registers as 64 bit is only supported for TCP communication.

      So it is not possible to read out the register for total Energy over RTU communication.