Orno OR-WE-504 Energy Meter
Content languageEnglish
Description
Read values of the Orno OR-WE-504 energy meter via Modbus RTU. This basic 1-phase energy meter (max 80A) is not MID certified.
Inputs and outputs · 5
| Name | Type | Unit |
|---|---|---|
| Voltage | Modbus | V |
| Active Power | Modbus | kW |
| Total Active Energy | Modbus | kWh |
| Current | Modbus | A |
| Power Factor | Modbus | <v.1> |
FAQ
No questions have been answered yet.
Questions and answers
Failed to read from WE-504
OpenDear Creator, we already configured the modbus address of the we-504 with the avtmod03 device. We can read any values with avtmod03 device from WE-504, but we cannot read values via the modbus extension using your template. We double checked everything, but no success... What should we miss, are there any limitations, any software version restriction or something else? Thank you for your help, regards, Laszlo
1 reply
Hello Laszlo, I don't see what could go wrong. This may be a silly question, but since you changed the Orno WE-504 Modbus address, did you change it as well in Loxone? Because in the template, the default Modbus address is 1.
Log in to rate, comment or ask a question. Log in