OpenEMS
Content languageEnglish
Description
This template is written to facilitate reading all avaliable data from OpenEMS based devices such as the Fenecon Pro Hybrid 10 via Modbus TCP.
The implementation is based upon the official API documentation.
For the energy manager, use the virtual inputs:
- sum_GridActivePower for Gpwr - sum_ProductionActivePower for Ppwr - sum_EssDischargePower for Spwr - sum_EssSoc for Soc
Use other virtual inputs for other specific needs.
Inputs and outputs · 39
| Name | Type | Unit |
|---|---|---|
| sum_State | Modbus | <v> |
| sum_EssSoc | Modbus | % |
| sum_EssActivePower | Modbus | kW |
| sum_GridActivePower | Modbus | kW |
| sum_GridMinActivePower | Modbus | kW |
| sum_GridMaxActivePower | Modbus | kW |
| sum_GridActivePowerL1 | Modbus | kW |
| sum_GridActivePowerL2 | Modbus | kW |
| sum_GridActivePowerL3 | Modbus | kW |
| sum_ProductionActivePower | Modbus | kW |
| sum_ProductionMaxActivePower | Modbus | kW |
| sum_ProductionAcActivePower | Modbus | kW |
| sum_ProductionMaxAcActivePower | Modbus | kW |
| sum_ProductionDcActualPower | Modbus | kW |
| sum_ProductionMaxDcActualPower | Modbus | kW |
| sum_ConsumptionActivePower | Modbus | kW |
| sum_ConsumptionMaxActivePower | Modbus | kW |
| sum_EssActivePowerL1 | Modbus | kW |
| sum_EssActivePowerL2 | Modbus | kW |
| sum_EssActivePowerL3 | Modbus | kW |
| sum_ProductionAcActivePowerL1 | Modbus | kW |
| sum_ProductionAcActivePowerL2 | Modbus | kW |
| sum_ProductionAcActivePowerL3 | Modbus | kW |
| sum_ConsumptionActivePowerL1 | Modbus | kW |
| sum_ConsumptionActivePowerL2 | Modbus | kW |
| sum_ConsumptionActivePowerL3 | Modbus | kW |
| sum_EssActiveChargeEnergy | Modbus | kWh |
| sum_EssActiveDischargeEnergy | Modbus | kWh |
| sum_GridBuyActiveEnergy | Modbus | kWh |
| sum_GridSellActiveEnergy | Modbus | kWh |
| sum_ProductionActiveEnergy | Modbus | kWh |
| sum_ProductionAcActiveEnergy | Modbus | kWh |
| sum_ProductionDcActiveEnergy | Modbus | kWh |
| sum_ConsumptionActiveEnergy | Modbus | kWh |
| sum_EssDcChargeEnergy | Modbus | kWh |
| sum_EssDcDischargeEnergy | Modbus | kWh |
| sum_GridMode | Modbus | <v> |
| sum_EssReactivePower | Modbus | kW |
| sum_EssDischargePower | Modbus | kW |
FAQ
No questions have been answered yet.
Questions and answers
EssActivePower wrong Values
OpenHi,
the Modbus Value on Register 303 brings a wrong Value. It is not the actual Battery Power.
Pls help.
2 replies
You Need Register 415 for the Battery
Hey, as basically already proposed, use instead the virtual input `sum_EssDischargePower`from the plugin which reads the register 415.
Modbus Register
OpenIn deinem Artikel schreibst du das das Register EssActiveDischargeEnergy die aktuelle Batterie Entladeenergie anzeigt leider ist das in Loxone die gesamte Entladeenergie der Lebenszeit des Speichers. Ich finde leider nirgends die aktuelle Entladeleistung weißt du das register bzw. die Adresse des Registers?
1 reply
Ich nutze dafür aus dem Plugin den virtuellen Eingang `sum_EssDischargePower`der das Register 415 abfragt.
Für eine Beschreibung der Register, gehe auf deine openEMS Instanz unter Einstellungen -> Anlagenprofil -> Konfiguration -> Modbus/TCP lesend und klicke auf `Download Protocoll`.
netzdienliche Beladung
OpenKönnte man bitte die netzdienliche Beladung (Manuell / Automatisch inkl. der 3 Risikobereitschafts Einstellungen / Aus) als schreibzugriff von Loxone an Fenecon integrieren?
No replies
Log in to rate, comment or ask a question. Log in
Ratings and comments
No ratings or comments yet.
Log in to rate, comment or ask a question. Log in