Template

Mitshubishi Heat Pump

by Drahoslav OndruskaNo rating yet1,349 downloads

Content languageEnglish

Description

Control and read out values from your Mitsubishi heat pump via Modbus. MelcoBEMS MINI (A1M) interface is required to enable Modbus RTU communication with Mitsubishi heat pump.

Developed and tested on heat pump model profile FTC6 and MelcoBEMS Mini (A1M) firmware version 3.0.25.

Inputs and outputs · 56

NameTypeUnit
Flow TempModbusºC
Operating Mode DHWModbus<v>
Ecodan On-OffModbus<v>
Tank Water Temp ActualModbusºC
Heating Mode – Zone 1Modbus<v>
Heating Mode – Zone 2Modbus<v>
Heat Pump On-OffModbus<v>
Return TempModbusºC
Flow Temp Zone 1ModbusºC
Flow Temp Zone 2ModbusºC
Return Temp Zone 1ModbusºC
Return Temp Zone 2ModbusºC
Water Pump 1Modbus<v>
Water Pump 2Modbus<v>
Flow RateModbusl/min
Last Measured Heating Consumption 1ModbuskWh
Last Measured DHW Consumption 1ModbuskWh
Energy Consumption Measured DayModbus<v>
Energy Consumption Measured MonthModbus<v>
Energy Consumption Measured YearModbus<v>
Energy Production Measured DayModbus<v>
Energy Production Measured MonthModbus<v>
Energy Production Measured YearModbus<v>
Last Measured Heating Production 1ModbuskWh
Last Measured DHW Production 1ModbuskWh
Consumed Power (actual)ModbuskW
Produced Power (actual)ModbuskW
Flow Temp Setpoint Zone 1ModbusºC
Flow Temp Setpoint Zone 2ModbusºC
Tank Water Temp TargetModbusºC
DHW ProhibitedModbus<v>
Heating Zone 1 ProhibitedModbus<v>
Heating Zone 2 ProhibitedModbus<v>
DHW Temperature DropModbusºC
Last Measured DHW Consumption 2ModbuskW
Last Measured Heating Consumption 2ModbuskW
Last Measured DHW Production 2ModbuskW
Last Measured Heating Production 2ModbuskW
Display Error Code Digit 1Modbus<v>
Display Error Code Digit 2Modbus<v>
Booster Heater 1Modbus<v>
Booster Heater 2Modbus<v>
Water Pump 3Modbus<v>
Force DHWModbus<v>
HolidayModbus<v>
Legionella PreventionModbus<v>
Heat Source Phase DHWModbus<v>
Modbus CounterModbus<v>
Set Zone 1 ThermostatModbusºC
Set Zone 2 ThermostatModbusºC
Set Zone 1 Heating ModeModbus<v>
Set Zone 2 Heating ModeModbus<v>
Set DHW ModeModbus<v>
Set Ecodan On-OffModbus<v>
Force DHWModbus<v>
Set Tank Water TemperatureModbusºC

FAQ

No questions have been answered yet.

Ratings and comments

No ratings or comments yet.

Questions and answers

  1. Is there also an template, example ?

    Open

    I have a mitshubishi heatpump , a mitshubishi A/C , loxone Valves, connected with modbus RTU Is there also a Template so that I can understand all the connections that the software makes

    Thx

    1 reply

    1. You can get the modbus template by clicking the download button. The template is only an interface to the heat pump and enables to read the values from the heat pump (sensors) or control the heat pump (actors).

      The user itself must implement an integration with temperature sensors, intelligent room controllers and other function blocks in Loxone Config.

      If you are interested in my config example, I can attach snapshots from my Loxone App and config file from my project. Unfortunately everything is in Slovak language only. Please email me at [email protected].

  2. Control the heat pump with loxone

    Open

    I have a mitsubishi EcoDan heat pump and loxone systems connected through Modbus MelcoBems Mini module with the heat pump. I have one floor heating system. In the loxone the hole configuration according the temperature control with intelligent room controller and flow temperature calculator is done and seems to work. I am not sure about setting the target temperature for heating to the mitsubishi EcoDan based on the output from loxone. Now I have set the A/C mode register 28 to 1 (heating flow Temp) and then based on the temperature calculated from the flow temperature calculator I set the value to register 33 (H/C Thermostat Target Temperature). I see on the Ecodan display that the value changes, so there is a reaction, but not sure if I am setting the right value to Ecodan ? Is this the correct way ? This works only with register No 33. I tried to set register 54 (Thermostat Target Temperature –Zone 1) but didn't succeed.

    Maybe you can provide me some examples or tips ?

    Thanks in advance Rafal [email protected]

    No replies

Report this entry

Report abuse

You have to be logged in to report an entry. Log in