LG PDRYCB500
Content languageEnglish
Description
How to set up the Modbus Address: https://www.manualslib.de/manual/700321/Lg-V-Net-Pdrycb500.html?page=11#manual IMPORTANT: You have to reboot the LG device, otherwise it will not take over the new Modbus address
Full manual: https://www.manualslib.de/manual/700321/Lg-V-Net-Pdrycb500.html#manual
Modbus settings:
You will see that the register addresses are not the same as in Loxone Config This is because you have to remove the 30000-40000 and subtract 1
Example: Operation is 1 - 1 = 0 Indoor temperature is 30003 - 30000 & 1 = 2 Set Run Mode is 40001 - 40000 & 1 = 0 Set Temperature is 40002 - 40000 & 1 = 1 Set Fan Speed is 40015 - 40000 & 1 = 14
Inputs and outputs · 10
| Name | Type | Unit |
|---|---|---|
| Status On_Off | Modbus | |
| Room_Temp | Modbus | ºC |
| Error Alarm (CH) | Modbus | <v.1> |
| SetPoint Temperature | Modbus | <v.1> |
| Mode_Status | Modbus | <v.1> |
| SetFanSpeed_Status | Modbus | <v.1> |
| On_Off | Modbus | |
| Setp_point_Temp | Modbus | <v.1> |
| SetMode | Modbus | <v.1> |
| SetFanSpeed | Modbus | <v.1> |
FAQ
No questions have been answered yet.
Questions and answers
BLOC
Openj ai utilisé ton projet mais sur une LG différente tu as mis ca sur quel bloc de contrôle. c 'est ma première lg tu as une capture de loxone config ou pas ? merci
No replies
config
OpenBonjour Dimitri,
J'aimerais utiliser votre modèle pour contrôler le climatiseur LG via Loxone avec Modbus. Est-ce que vous avez aussi une config pour cela ? Vous pouvez l'envoyer à [email protected]
Merci d'avance !
Salutations,
Hans Mens
1 reply
Hello, There is currently no sample file available from Loxone. Which device model from LG do you want to integrate with this? Is it an AC air conditioner or a heat pump? If you integrate it successfully, please get in touch with me.
Thank you very much