Lambda Heating & Cooling
Content languageEnglish
Description
This template allows you to control your Lambda Air-Water Heatpump without Gateway over Modbus TCP or RTU. There are three different ways how to connect Lambda with Loxone:
- Direct to the Heatpump without Gateway using Modbus TCP - Direct to the Heatpump without Gateway using Modbus RTU with Loxone Modbus Extension - Direct to the Heatpump without Gateway using Modbus RTU and Loxone Modbus Air.
Depending on variation of your project you can choose between Miniserver, Miniserver Go or Miniserver Compact.
The choice of paring Lambda Heatpumps with Loxone offers the possibility of:
- Integrating demand-based heating and cooling depending on e.g. presence or the protection of open windows - Active integration in interaction with e.g. PV- systems in a Loxone Energy Management - Using flexible electricity tariffs with the Spot Price Optimizer. - Use statistics or individual notifications - Create your own individual schematics - Reduce cycles and operating hours of your Lambda heatpump - Combining hybrid solutions e.g. Heatpump and PV- Heating element in your Hot Water Storage - Create e.g. yearly operation goals like certain annual runtime forces for hybrid systems e.g. (Heatpump 65% amount of energy, Gas heater 35% amount of energy) to fulfill the requirements of your local government. - Grid management according to §14a ENWG in Germany - In addition to the electrical power, the current and total thermal energy can also be visualized via the Loxone Energy Flow Monitor. To the compact overview for e.g. contractors. - Influence on the hot water circulation pump by controlling via the presence detectors. - Increased security through leakage detection or activation of IP cameras in the plant room.
With our step by step manual for collecting the heating or cooling demand and forwarding it to the Lambda Heatpump, we enable the interaction of the individual room control with the central heating/cooling system of Lambda.
Structure:
Lambda Helpcenter, download area and activation of Modbus:
- In our download area you can find the always actual document Modbus Instructions for activation and full datapoints.
- In our download area you can also find the always actual manual how to deal with the operating system of Lambda.
- You can find your schematic unter the following link: principal Lambda schematics
All documents are available in German. For further information please get in touch with our support. Tel.: +43 (0)50 6322 200 E-Mail: [email protected]
Example UseCase: Residential building with Heating & Cooling Buffer, Hot Water Storage and two mixed heating circuits.
- Lambda Air-Water Heatpump EU13L - Heat/Cool Buffer storage - Hot Water Storage --> Controlled by Loxone - Mixing Circuit Heating (e.g. underfloor)--> Controlled by Loxone - Mixing Circuit Heating/Cooling (e-.g. ceiling) --> Controlled by Loxone
Schematic 112_000:
Inputs and outputs · 36
| Name | Type | Unit |
|---|---|---|
| 3001 State Operating Mode Heat/Cool Buffer | Modbus | <v> |
| 3002 Actual Heat/Cool Buffertemperature Top | Modbus | °C |
| 3003 Actual Heat/Cool Buffertemperature Bottom | Modbus | °C |
| 2001 State Operating Mode Hot Water Storage | Modbus | <v> |
| 2002 Actual Hot Water Storage Temperature Top | Modbus | °C |
| 2003 Actual Hot Water Storage Temperature Bottom | Modbus | °C |
| 5001 State Operating Mode HC1 | Modbus | <v> |
| 5002 Actual Supply Flowtemperature HC1 | Modbus | °C |
| 0103 Actual Heatpump Power Consumption | Modbus | kW |
| 0002 Actual Outsidetemperature | Modbus | °C |
| 0003 Actual Outsidetemperature average | Modbus | °C |
| 1000 State Heatpump Error | Modbus | <v> |
| 1002 State Heatpump Operation State | Modbus | <v> |
| 1003 State Heatpump Operation Mode | Modbus | <v> |
| 1004 Actual Heatpump Supply Flowtemperature | Modbus | °C |
| 1005 Actual Heatpump Return Flowtemperature | Modbus | °C |
| 1006 Actual Heatpump Flow Rate | Modbus | l/min |
| 1007 Actual Heatpump Outdoorsuctiontemperature | Modbus | °C |
| 1011 Actual Heatpump Inverter Thermal Power | Modbus | kW |
| 1012 Actual Heatpump Inverter Electrical Power | Modbus | kW |
| 1013 Actual Heatpump COP | Modbus | <v.2> |
| 1001 State Heatpump Error number | Modbus | <v> |
| 2050 State Hot Water Targettemperature | Modbus | °C |
| 1019 State Relais Request Contact additional heat generator | Modbus | <v> |
| 5102 Actual Supply Flowtemperature HC2 | Modbus | °C |
| 5101 State Operating Mode HC2 | Modbus | °C |
| 5050 State Offset Flow Line Temperature HC1 | Modbus | °C |
| 5150 State Offset Flow Line Temperature HC2 | Modbus | °C |
| 2050 Hot Water Storage Targettemperature | Modbus | °C |
| 5005 Target Supplyflowtemperature HC1 | Modbus | °C |
| 0102 Actual Input Power-General E-Manager | Modbus | kW |
| 5006 Target Operating Mode HC1 | Modbus | <v> |
| 5105 Target Supplyflowtemperature HC2 | Modbus | °C |
| 5106 Target Operating Mode HC2 | Modbus | <v> |
| 5050 Offset Target Supplyflowtemperature HC1 | Modbus | °C |
| 5150 Offset Target Supplyflowtemperature HC2 | Modbus | °C |
FAQ
No questions have been answered yet.
Questions and answers
Falsche Adresse hinterlegt
OpenGuten Tag
Im File: Lambda Sample File.Loxone Loxone File • 163KB
Ist bei der 0002 Actual Outsidetemperature die Adresse 2002 hinterlegt statt die 2, und die Kommastelle ist auch nicht ganz korrekt.
Vielen Dank dass Sie eine Vorlage für Ihr Produkt erstellt haben. Freundliche Grüsse Lukas Dreyer ETM GmbH