Lambda Heating & Cooling

by LAMBDA WarmepumpenNo rating yet738 downloads

Content languageEnglish

Description

This template allows you to control your Lambda Air-Water Heatpump without Gateway over Modbus TCP or RTU. There are three different ways how to connect Lambda with Loxone:

- Direct to the Heatpump without Gateway using Modbus TCP - Direct to the Heatpump without Gateway using Modbus RTU with Loxone Modbus Extension - Direct to the Heatpump without Gateway using Modbus RTU and Loxone Modbus Air.

Depending on variation of your project you can choose between Miniserver, Miniserver Go or Miniserver Compact.


The choice of paring Lambda Heatpumps with Loxone offers the possibility of:

- Integrating demand-based heating and cooling depending on e.g. presence or the protection of open windows - Active integration in interaction with e.g. PV- systems in a Loxone Energy Management - Using flexible electricity tariffs with the Spot Price Optimizer. - Use statistics or individual notifications - Create your own individual schematics - Reduce cycles and operating hours of your Lambda heatpump - Combining hybrid solutions e.g. Heatpump and PV- Heating element in your Hot Water Storage - Create e.g. yearly operation goals like certain annual runtime forces for hybrid systems e.g. (Heatpump 65% amount of energy, Gas heater 35% amount of energy) to fulfill the requirements of your local government. - Grid management according to §14a ENWG in Germany - In addition to the electrical power, the current and total thermal energy can also be visualized via the Loxone Energy Flow Monitor. To the compact overview for e.g. contractors. - Influence on the hot water circulation pump by controlling via the presence detectors. - Increased security through leakage detection or activation of IP cameras in the plant room.

With our step by step manual for collecting the heating or cooling demand and forwarding it to the Lambda Heatpump, we enable the interaction of the individual room control with the central heating/cooling system of Lambda.


Structure:


Lambda Helpcenter, download area and activation of Modbus:

- In our download area you can find the always actual document Modbus Instructions for activation and full datapoints.

- In our download area you can also find the always actual manual how to deal with the operating system of Lambda.

- You can find your schematic unter the following link: principal Lambda schematics

All documents are available in German. For further information please get in touch with our support. Tel.: +43 (0)50 6322 200 E-Mail: [email protected]


Example UseCase: Residential building with Heating & Cooling Buffer, Hot Water Storage and two mixed heating circuits.

- Lambda Air-Water Heatpump EU13L - Heat/Cool Buffer storage - Hot Water Storage --> Controlled by Loxone - Mixing Circuit Heating (e.g. underfloor)--> Controlled by Loxone - Mixing Circuit Heating/Cooling (e-.g. ceiling) --> Controlled by Loxone

Schematic 112_000:

Inputs and outputs · 36

NameTypeUnit
3001 State Operating Mode Heat/Cool BufferModbus<v>
3002 Actual Heat/Cool Buffertemperature TopModbus°C
3003 Actual Heat/Cool Buffertemperature BottomModbus°C
2001 State Operating Mode Hot Water StorageModbus<v>
2002 Actual Hot Water Storage Temperature TopModbus°C
2003 Actual Hot Water Storage Temperature BottomModbus°C
5001 State Operating Mode HC1Modbus<v>
5002 Actual Supply Flowtemperature HC1Modbus°C
0103 Actual Heatpump Power ConsumptionModbuskW
0002 Actual OutsidetemperatureModbus°C
0003 Actual Outsidetemperature averageModbus°C
1000 State Heatpump ErrorModbus<v>
1002 State Heatpump Operation StateModbus<v>
1003 State Heatpump Operation ModeModbus<v>
1004 Actual Heatpump Supply FlowtemperatureModbus°C
1005 Actual Heatpump Return FlowtemperatureModbus°C
1006 Actual Heatpump Flow RateModbusl/min
1007 Actual Heatpump OutdoorsuctiontemperatureModbus°C
1011 Actual Heatpump Inverter Thermal PowerModbuskW
1012 Actual Heatpump Inverter Electrical PowerModbuskW
1013 Actual Heatpump COPModbus<v.2>
1001 State Heatpump Error numberModbus<v>
2050 State Hot Water TargettemperatureModbus°C
1019 State Relais Request Contact additional heat generatorModbus<v>
5102 Actual Supply Flowtemperature HC2Modbus°C
5101 State Operating Mode HC2Modbus°C
5050 State Offset Flow Line Temperature HC1Modbus°C
5150 State Offset Flow Line Temperature HC2Modbus°C
2050 Hot Water Storage TargettemperatureModbus°C
5005 Target Supplyflowtemperature HC1Modbus°C
0102 Actual Input Power-General E-ManagerModbuskW
5006 Target Operating Mode HC1Modbus<v>
5105 Target Supplyflowtemperature HC2Modbus°C
5106 Target Operating Mode HC2Modbus<v>
5050 Offset Target Supplyflowtemperature HC1Modbus°C
5150 Offset Target Supplyflowtemperature HC2Modbus°C

FAQ

No questions have been answered yet.

Ratings and comments

No ratings or comments yet.

Questions and answers

  1. Falsche Adresse hinterlegt

    Open

    Guten Tag

    Im File: Lambda Sample File.Loxone Loxone File • 163KB

    Ist bei der 0002 Actual Outsidetemperature die Adresse 2002 hinterlegt statt die 2, und die Kommastelle ist auch nicht ganz korrekt.

    Vielen Dank dass Sie eine Vorlage für Ihr Produkt erstellt haben. Freundliche Grüsse Lukas Dreyer ETM GmbH

    No replies