Komfovent DOMEKT C6M
Content languageEnglish
Description
The product range includes vertical, horizontal, and flat configurations equipped with either rotary or counterflow plate heat exchangers. All units are built around advanced control systems that optimize ventilation, heating, cooling, and air quality while keeping operational costs low.
The integrated C6M control platform provides intuitive operation for everyday users and extensive configuration options for HVAC professionals. The core philosophy behind the design of C6M – the ventilation unit would operate properly without constant adjustments from the user. Ventilation modes are optimized for daily use and can switch automatically according to air quality or user-defined schedules.
Advanced features support both comfort and efficiency: · Flexible airflow control, including CAV, VAV, and DCV modes · Temperature management with supply, extract, and room-based control strategies · Automatic air quality control via CO₂ and humidity sensors · Seasonal energy-saving functions such as cool recovery, free cooling, and temperature saving · Support for external devices, including water coils and DX units · Weekly and holiday schedules, timed modes, and on-demand ventilation · Comprehensive safety and protection mechanisms (frost protection, overheat protection, fire alarms, and critical temperature shutdown) · Smart diagnostics, filter status monitoring, and detailed energy counters Connectivity options include a web interface and cloud-based smartphone control enabling remote operation, monitoring, firmware updates, and service diagnostics. Integrated Modbus TCP/IP protocol is compatible with Loxone devices as well. Together, these features ensure that DOMEKT units deliver reliable, efficient, and user-friendly ventilation suited for modern residential environments.
For more information on DOMEKT residential units, please visit Komfovent webpage
Inputs and outputs · 47
| Name | Type | Unit |
|---|---|---|
| Return water temperature | Modbus | °C |
| Current mode | Modbus | <v> |
| Active alarms count | Modbus | <v> |
| Exhaust temperature | Modbus | °C |
| Supply temperature | Modbus | °C |
| Current supply flow | Modbus | <v> |
| Current extract flow | Modbus | <v> |
| ON/OFF status | Modbus | <v> |
| ECO mode | Modbus | <v> |
| AUTO mode | Modbus | <v> |
| Current supply fan intensivity | Modbus | % |
| Current extract fan intensivity | Modbus | % |
| Power consumption | Modbus | W |
| Energy saving | Modbus | % |
| Heat exchanger efficiency | Modbus | % |
| Heater power | Modbus | W |
| Heat exchanger recovery | Modbus | W |
| Heat exchanger | Modbus | % |
| Panel 2 humidity | Modbus | % |
| Extract temperature | Modbus | °C |
| Filters Impurity | Modbus | % |
| Water cooler | Modbus | % |
| Electric heater | Modbus | % |
| Water heater | Modbus | % |
| DX unit | Modbus | % |
| Outdoor temperature | Modbus | °C |
| Panel 2 temperature | Modbus | °C |
| Panel 1 temperature | Modbus | °C |
| Panel 1 humidity | Modbus | % |
| Connected panels | Modbus | <v> |
| Sensor 1 (B8) | Modbus | <v> |
| Sensor 2 (B9) | Modbus | <v> |
| Active alarm 1 code | Modbus | <v> |
| Active alarm 2 code | Modbus | <v> |
| Active alarm 3 code | Modbus | <v> |
| Set Current mode | Modbus | <v> |
| Set ON/OFF status | Modbus | <v> |
| AUTO mode | Modbus | <v> |
| ECO mode | Modbus | <v> |
| Boost (Temperature setpoint) | Modbus | °C |
| Scheduler operation mode | Modbus | <v> |
| Temperature control mode | Modbus | <v> |
| Intensive (Temperature setpoint) | Modbus | °C |
| Away (Temperature setpoint) | Modbus | °C |
| Normal (Temperature setpoint) | Modbus | °C |
| Clean filters calibration | Modbus | <v> |
| Reset active alarms | Modbus | <v> |
FAQ
No questions have been answered yet.
Questions and answers
Is this tempalte also working for the the C5 Controller?
OpenGood day, For the joint municipality of Sottrum, we require the integration of several ventilation units with Komfovent C5 and C6 controllers. I noticed in the Loxone Library that there is a plugin available for the Komfovent DOMEKT C6M. Can this plugin also be used for other ventilation units with C5 controllers? The following combinations of climate units and controllers are present in the customer’s system:
Komfovent Domekt CF 700 HL1 C6M with C6 control
Komfovent Verso CF 1000 H W R1 with C5 control
Komfovent Verso CF 1300 H W L1 with C5 control
Komfovent Verso R 1000 FSA C5 with C5 control
If you have any questions, please do not hesitate to contact me.
Best regards, Bernd Viets
1 reply
Hello,
This library is for C6M controllers. Unfortunately, it will not work with C5 controllers. Because the control logic, parameters, functions, modbus registers of these controllers are different.
Any chnces for C5 template?
OpenHello,
Will you prepare a template for integrating the C5 controller?
1 reply
Hello,
Yes, we plan to prepare a library and template for C5 controller as well.
Template
Openhello I use this template today. But I can't change temperature. Later I found in correction of values mistakes you have 50>5 and 400>40 but correctly is it 5>50 and 40>400
1 reply
Hello, We will check and correct the template.
Thank you for your comment!
Komfovent turn off after restart the Loxone
OpenHello, What should I set so that the Komfovent control unit does not turn off after restarting the Loxone 1 miniserver? BR
2 replies
Hello,
To do this you need to remove the On/Off condition from the AC Unit controller and add a simple On/off switch.
We will prepare a sample and upload it soon.
Thank you for your comment!
Hi, adding a simply On/Off switch doesn't help. Each save/restart of the miniserver turns off the recuperator for a moment and turns it on again.