iQntrol DOS-MODBUS dosing system
Content languageEnglish
Description
The iQontrol DOS-MODBUS is a Modbus-capable chlorine dosing system for reliable compliance with the water quality and disinfection. Self-priming peristaltic metering pumps inject disinfectants and pH regulators directly into the sample water flowing through.
FUNCTIONS
- fully automatic measure, control & dosing of pH / Redox values within the Loxone application - a redox electrode with large, self-cleaning platinum probe reliably responds to changes in the water quality - temperature sensor for temperature measurement - water flow monitoring with switch-off function in case of water shortage - fault and alarm monitoring - automatic level monitoring of the disinfectants canisters - data recording for statistical purposes
INTERFACES
- Modbus TCP - input for external release - relay 230 V for the control of the pool heating with non-volt changeover contact - alarm relay with non-volt changeover contact
ONE POOL. ONE SYSTEM. ONE SMART HOME APP. The iQntrol DOS-MODBUS is part of the iQnnect pool system. iQnnect by Peraqua is an exquisite range of intelligently networked pool components for a fully automatic and device-controlled pool. The pool technology components are integrated into the system and linked with one another using Modbus, DMX, AO, or similar extensions. This enables many functions to be controlled in just one app.
More on Peraqua
Inputs and outputs · 55
| Name | Type | Unit |
|---|---|---|
| 16 - Temperature | Modbus | °C |
| 38- pH - p-range | Modbus | <v.2> |
| B02 - disinfection empty | Modbus | |
| B03 - pH regulation empty | Modbus | |
| B32 - pH min Alarm | Modbus | |
| B33 - pH max Alarm | Modbus | |
| B13 - no flow | Modbus | |
| B16 - pH regulation leak | Modbus | |
| B17 - disinfection leak | Modbus | |
| B36 - mV min Alarm | Modbus | |
| B37 - mV max. Alarm | Modbus | |
| B41 - IO-Board F1 fuse fault (24V Desinfektion) | Modbus | |
| B44 - IO-Board F2 fuse fault (24V pH) | Modbus | |
| B45 - NT-Board F1 fuse fault (24V Sensoren) | Modbus | |
| B48 - pH regulation dynamic dosing exceeded | Modbus | |
| B50 - disinfection dynamic dosing exceeded | Modbus | |
| B51 - dosing OFF | Modbus | |
| B64 - disinfection dosing 24V | Modbus | |
| B65 - pH regulation dosing 24V | Modbus | |
| B66 - flocculation dosing | Modbus | |
| B18 - flocculation emty | Modbus | |
| B19 - flocculant leak | Modbus | |
| B68 - alarm | Modbus | |
| B70 - pH regulation dosing 230V | Modbus | |
| B71 - disinfection dosing 230V | Modbus | |
| C00 - pH control direction | Modbus | |
| C02 - flocculation ON_OFF | Modbus | |
| C03 - mutual locking ON_OFF | Modbus | |
| C16 - Modus Automatic_Menu | Modbus | |
| 22 - pH | Modbus | pH |
| 24 - Redox | Modbus | mV |
| 36 - pH - setpoint | Modbus | <v.2> |
| 40 - pH - alarm low | Modbus | <v.2> |
| 42 - pH - alarm high | Modbus | <v.2> |
| 44 - pH - time watch | Modbus | <v.2> |
| 46 - pH - Control types | Modbus | <v.2> |
| 48 - mV - setpoint | Modbus | <v.2> |
| 50 - mV - p-range | Modbus | <v.2> |
| 52 - mV - alarm low | Modbus | <v.2> |
| 54 - mV - alarm high | Modbus | <v.2> |
| 56 - mV - time watch | Modbus | <v.2> |
| 58 - mV_ml - Control types | Modbus | <v.2> |
| 114 - Dosing delay | Modbus | s |
| 36 - pH - setpoint | Modbus | <v.2> |
| C16 - Modus Automatic_Menu | Modbus | |
| 38- pH - p-range | Modbus | <v.1> |
| 40 - pH - alarm low | Modbus | <v.1> |
| 42 - pH - alarm high | Modbus | <v.1> |
| 44 - pH - time watch | Modbus | <v.1> |
| 48 - mV - setpoint | Modbus | <v.1> |
| 50 - mV - p-range | Modbus | <v.1> |
| 52 - mV - alarm low | Modbus | <v.1> |
| 54 - mV - alarm high | Modbus | <v.1> |
| 56 - mV - time watch | Modbus | <v.1> |
| 114 - Dosing delay | Modbus | <v.1> |