Hoval District Heating
Content languageEnglish
Description
Hoval with the TopTronic® E operating system can be connected to Loxone via multiple HovalConnect Gateways (GW). Please note that, starting in July 2026, we have enabled all Hoval gateways—whether "LAN", "Wi-Fi", "Modbus", "OPCUA", or "KNX" —to support the Modbus interface via an over-the-air update from HovalConnect. The RTU terminal block is included on the HovalConnect Modbus Gateway (article number 6049501) as standard, or can be ordered optionally from Hoval (article number 2062935). If you only need cost-effective integration via Modbus TCP, the HovalConnect LAN Gateway (article number 6049496) is sufficient! This means that all existing systems and new Hoval systems come with Loxone connectivity right out of the box, so there’s no need to purchase any additional hardware!
There are four different ways how to connect Hoval with Loxone: 1.Hoval Modbus TCP
2.Hoval Modbus RTU Gateway with Loxone Modbus Extension
3.Hoval Modbus RTU Gateway with a Loxone Modbus Air.
4.Hoval Modbus RTU Gateway with a Loxone Modbus Tree.
Depending on variation of your project you can choose between Miniserver, Miniserver Go or Miniserver Compact The Hoval TopTronic E (TTE) is a operating system for Hoval District Heating, Air/Water, Brine/Water, Water/Water Heatpumps, Gas, Oil and wood sources that are able to Heat or Cool by stand alone or combining them to Hybridsystems.
- The Hoval Top Tronic E (TTE) is also able to operate his own ventilation system. - The Hoval Top Tronic E (TTE) is also able to communicate with the Hoval PV-Heater. - The Hoval Top Tronic E (TTE) is also able for full integration of e.g. heatpumps with Hoval Heating & Cooling - The Hoval Toop Tronic E (TTE) also offers the option of simple connectivity with PV inverters with Hoval Energy Management
The choice of paring District Heating Stations with Loxone offers the possibility of:
- Integrating demand-based heating depending on e.g. presence or the protection of open windows, Automatic Shading and Weatherforecast. - Use statistics or individual notifications - Create individual system schematics. - Create Hybrid Systems with other Hoval Sources or the Hoval PV-Heater. - Use the flexible ways of reading thermal heat meters and electricity meters via e.g. M-Bus or IR readers and the thermal or electrical visualization in the Loxone Energy Flow Monitor. For e.g. Contractors. - Whether residential or commercial buildings. No matter whether Hoval-TTE or Loxone is the main operator, no matter which hydraulics and consumers. Connecting Hoval with Loxone systems allows the demand-oriented and intelligent distribution of energy thanks to distribution solutions from Belimo or IMI TA. - Influence on the hot water circulation pump by controlling via the presence detectors. - Increased security through leakage detection or activation of IP cameras in the plant room. - Use of the District Heating Station to operate a Pool and to automatically control the switching of heating, Pool and hot water. - Connectivity and setup of heating centers and heating substations with the flexible ways of Loxone intercommunication.
Hoval District Heating with Hoval Supervisor:
System overview example using Modbus TCP:
If a District Heating Station, another Heating Source ore more, or a Ventilation unit are in a CAN bus network, one Modbus Gateway (6049501) is sufficient to control both systems by using different Modbus register addresses.
Hoval helpcenter, download area and activation of Modbus:
- If you need help with e.g. the configuration of Modbus within the Hoval Control unit please contact our local departments. - Hoval Integrate CH ([email protected]) - Hoval Integrate AT ([email protected]) - Hoval Integrate DE ([email protected]) - You have to use the direct download of documents on the Hoval Homepage. Therefore, the instructions in the download area of the template must be used and checked for the latest version. - To activate Modbus TCP on the Control unit of your Hoval Source, please follow the Modbus TCP instructions e.g. "Praxisanleitung Hoval-Loxone Deutsch" in the download area of the template. Please always use the following link for a actual Modbus documentation because Hoval is constantly updating the documentation and expanding data points. You can find the modbus documentation here -> Modbus datapoint list - In addition to the data points of the UseCase to the Download Button, a german template of datapoints is also available in the download area of the Librarytemplate - For Remote Support reasons trough Hoval SmartServices and automatic software updates (Bugfixings & new datapoints) of the Gateway, please connect your HovalConnect Gateway with HovalConnect.
Example UseCase District Heating Station: Hoval Trans Therm Giro Heating Circuit 1: --> Controlled by Loxone moving the Room Target Setpoint Heating Circuit 2: --> Controlled by Loxone moving the Room Target Setpoint Heating Circuit 3: --> Controlled by Loxone moving the Room Target Setpoint Domestic Hot Water: --> Controlled by Loxone moving the Hot Water Setpoint Hoval PV Heater 3,5kW: --> Controlled by Loxone Energy Manager
Inputs and outputs · 45
| Name | Type | Unit |
|---|---|---|
| Aktuelle Außentemperatur Giro | Modbus | °C |
| Status Warmwasser Sollwert Giro | Modbus | °C |
| Aktuelle Warmwassertemperatur Oben | Modbus | °C |
| Status Warmwasserregelung Giro | Modbus | <v> |
| Status Heizkreisregelung HK1 | Modbus | <v> |
| Aktuelle Vorlaufisttemperatur HK1 | Modbus | °C |
| Aktuelle Mischerposition HK1 | Modbus | % |
| Status Mischkreispumpe HK1 | Modbus | <v> |
| Status Vorlaufsolltemperatur HK1 | Modbus | °C |
| Status Heizkreisregelung HK2 | Modbus | <v> |
| Aktuelle Vorlaufisttemperatur HK2 | Modbus | °C |
| Status Mischkreispumpe HK2 | Modbus | <v> |
| Status Vorlaufsolltemperatur HK2 | Modbus | °C |
| Aktuelle Mischerposition HK2 | Modbus | <v> |
| Status Heizkreisregelung HK3 | Modbus | <v> |
| Aktuelle Vorlaufisttemperatur HK3 | Modbus | °C |
| Aktuelle Mischerposition HK3 | Modbus | <v> |
| Status Mischkreispumpe HK3 | Modbus | <v> |
| Status Vorlaufsolltemperatur HK3 | Modbus | °C |
| Status Summensollvorlauftemperatur | Modbus | °C |
| Status Giro Primärventilstellung | Modbus | % |
| Aktuelle Primär Giro Vorlauftemperatur | Modbus | °C |
| Aktuelle Primär Giro Rücklauftemperatur | Modbus | °C |
| Aktuelle thermische Leistung LowByte | Modbus | kW |
| Aktuelle Energie HighByte | Modbus | MWh |
| Aktuelle Energie LowByte | Modbus | MWh |
| Aktueller Durchfluss LowByte | Modbus | l/h |
| DP "Aktuelle Vorlauftemperatur" M-Bus 2 | Modbus | °C |
| DP "Aktuelle Rücklauftemperatur" M-Bus 2 | Modbus | °C |
| DP "Info RLF" Allgemein | Modbus | °C |
| Aktuelle Sekundär Giro Vorlauftemperatur | Modbus | °C |
| DP "Info VF" Allgemein | Modbus | °C |
| DP "Info VF1" Allgemein | Modbus | °C |
| DP "Info SF1" Allgemein | Modbus | °C |
| Aktuelle Warmwassertemperatur Unten | Modbus | °C |
| Aktuelle Sekundär Giro Rücklauftemperatur | Modbus | °C |
| DP "Info VE6" Allgemein | Modbus | °C |
| Raum Soll Heizkreis 1 | Modbus | °C |
| Raum Soll Heizkreis 2 | Modbus | °C |
| Raum Soll Heizkreis 3 | Modbus | °C |
| Betriebswahl Heizkreis 3 | Modbus | <v> |
| Betriebswahl Heizkreis 2 | Modbus | <v> |
| Betriebswahl Heizkreis 1 | Modbus | <v> |
| Betriebswahl Warmwasser | Modbus | <v> |
| Warmwasser Soll | Modbus | °C |
FAQ
No questions have been answered yet.
Questions and answers
Probleme beim Download der Dokumentation und Frage zur Fehlercode-Übersicht
OpenGuten Tag
der Download bestimmter Dateien ist aktuell nicht möglich, insbesondere der Datei „Modbus Gateway + Datapoints [EN].PDF“.
Zudem möchte ich nachfragen, ob es eine Übersichtsliste bzw. Dokumentation gibt, aus der hervorgeht, welcher Fehlercode (0–255) des Datenpunkts „Status Fehlercode vom Automaten“ welcher konkreten Störung entspricht.
Ohne eine entsprechende Beschreibung der Fehlercodes ist es schwierig, die reinen Zahlen sinnvoll zu interpretieren oder eine fundierte Aussage zur jeweiligen Störung zu treffen.
Vielen Dank für Ihre Unterstützung. Ich freue mich auf Ihre Rückmeldung.
Freundliche Grüsse Dominik Schönenberger
1 reply
Hallo Herr Schönenberger,
Vielen Dank für den Hinweis. Dass PDF Dokumente manchmal nicht funktionieren ist leider ein kleiner Bug in der Loxone Library, wir haben die Dateien ausgetauscht, Sie können diese nun öffnen.
Zu Ihrer Frage bezüglich den Fehlercodes: Sie kommentieren hier das District Heating (Fernwärme) Template. Diese enthält keinen Datenpunkt mit einer Übersicht von 0-255 Fehlercodes. Das hat den Grund dass eine Hoval Fernwärmestation keinen "Funktionsautomaten" wie es z.B. eine Hoval Wärmepumpe oder Gaskessel besitzt, verbaut hat. Funktionsautomaten verbauen wir überall dort, wo Verbrennungen oder Kältetechnische Prozesse geregelt werden müssen. Deswegen gibt es dort auch unterschiedliche Fehlercodes.
Bei einer Fernwärmestation ist dies nicht notwendig, hier ist daher nur das Basismodul "Top Tronic E Fernwärme (TTE-FW)" verbaut. Daher gibt es auch keinen Datenpunkt diesbezüglich.
Besitzen Sie eine Wärmepumpe, Pellet, Gas oder Öl-Kessel, können Sie die Fehlercodes im Heating & Cooling Template in den Statusbausteinen finden.
Sollten Sie eine Hoval Fernwärmestation nutzen, gelten die Status Codes für: -Status Heizkreisregelung -Status Warmwasserregelung
Diese finden Sie im Template.
Sollten Sie weitere spezifische Fragen zu Datenpunkten oder Statuswerten haben, steht Ihnen unser Hoval Integrate Support zur Verfügung.
Für Deutschland --> [email protected] Für Österreich --> [email protected] Für Schweiz --> [email protected]
Mit freundlichen Grüßen Maximilian Stoll Produktmanagement Hoval
Support
OpenJede Hoval Anlage ist individuell. Wer unterstützt mich seitens Hoval bei Modbus, Datenpunkten, Softwareupdates und Funktionserklärungen?
1 reply
Hoval hat sich zum Dezember 2025 mit einem eigenen Support für externe Energie- & Home-Automation Systeme wie Loxone ausgerichtet.
Sie sind Endkunde, Elektriker, Systemintegrator oder Installateur? Dann melden Sie sich gerne in Ihrer Hoval Ländergesellschaft.
Ein Team aus Service- & MSR-Techniker unterstützt Sie bei Ihren Vorhaben.
Hoval Integrate CH --> https://www.hoval.ch/de_CH/hoval-integrate-landing-page ([email protected]) Hoval Integrate AT --> https://www.hoval.at/de_AT/hoval-integrate-landing-page ([email protected]) Hoval Integrate DE --> https://www.hoval.de/de_DE/hoval-integrate-landing-page ([email protected])
Modbus Schnittstellenaktivierung funktioniert nicht
OpenHallo,
Ich habe leider nur ein LAN Gateway, kann zwar am Hoval Display den Menüpunkt "Modbus" auswählen, es erscheinen aber keine Modbus Einstellparameter wie Protokoll (TCP oder RTU), Baudrate oder Parität.
An was kann das liegen?
Benötige ich nun extra ein HovalConnect Modbus Gateway?
1 reply
Hallo,
Über die Aufschaltung bzw. Registrierung der Anlage bei HovalConnect erhält das HovalConnect Gateway over the air automatisch Softwareupdates.
Im letzten Softwareupdate (Release Juli 2026) mit der Softwareversion 2.39.XX haben wir die Modbus Schnittstelle an allen HovalConnect Gateways (LAN, WLAN, KNX, OPCUA) freigeschaltet.
Das bedeutet Hoval Bestandsanlagen haben über das kostenlose Softwareupdate eine Modbus Schnittstelle erhalten und können ohne dem Einsatz eines teureren HovalConnect Modbus Gateway mit Loxone Miniserver gekoppelt werden.
Nach dem Softwareupdate werden also die Parameter im Menüpunkt "Modbus" sichtbar und es wird lediglich ein kosteneffizientes "LAN" Gateway benötigt, um die Konnektivität mit Loxone herzustellen.
Hoval ermöglicht durch die schnittstellenoffene Strategie über Hoval Integrate also die Konnektivität mit PV-Anlagen, Batteriespeicher, Wallboxen, PV-Heizstäben, dynamischen Stromtarifen, Netzdienlicher Steuerung (§14a), Lastmanagement, Energiegemeinschaften, Einzelraumregelungen, Bedarfsgeführter Erzeugung, Wettereinflüsse, Virtuellen Kraftwerken und vieles mehr!