Skip to content
Template

F&F Electricity energy meter LE-03MW

by Eskon-InzeneringNo rating yet519 downloads

Content languageEnglish

Description

Characteristis of the device 3-phase, 2-way energy meter; * direct measurement up to 80 A; * energy measurement in 4 tariff zones; * built-in real time clock with battery backup to switch tariff zones; * registration of total and divided into consumption tariffs: – total active and reactive energy; – active and reactive energy divided into individual quadrants; * 8 time schedules dividing the day into tariff zones; * it can settle energy according to schedules specific for business days and weekends; * it can divide year into 8 time intervals; in each interval the energy (for weekdays) can be settled according to a different schedule; * indication of network parameters (voltages, currents, active power, reactive power, apparent power, power factor, frequency); * calculation of power demand for individual tariffs; * an additional, resettable energy consumption meter; * compliance with MID; * RS-485 port, Modbus RTU protocol; * optical communication port compliant with EN62056 (IEC1107) standard; * 2× SO pulse outputs with a programmable number of pulses per kWh / kvarh. * multifunction LCD display.

Inputs and outputs · 67

NameTypeUnit
Consumed active energyModbuskWh
Exported active energyModbuskWh
Total reactive energyModbuskWh
Consumed reactive energyModbuskWh
L2 phase - consumed active energyModbuskWh
L2 phase - exported active energyModbuskWh
L2 phase - reactive energyModbuskWh
Active Energy Σ T2ModbuskWh
L1 phase - consumed active energyModbuskWh
L1 phase - exported active energyModbuskWh
L1 phase - reactive energyModbuskWh
L1 phase - consumed reactive energyModbuskWh
L3 phase - consumed active energyModbuskWh
L3 phase - exported active energyModbuskWh
L3 phase - reactive energyModbuskWh
Active Energy Σ T2, expModbuskWh
Total Active Energy Σ (T1_T2), impModbuskWh
Total Active Energy Σ (T1_T2), expModbuskWh
L1 Phase - active powerModbuskW
L2 Phase - active powerModbuskW
L3 Phase - active powerModbuskW
Active Power ΣModbuskW
Reactive Energy 1st phase T1, impModbuskvarh
Reactive Energy 2nd phase T1, impModbuskvarh
Reactive Energy 3rd phase T1, impModbuskvarh
Reactive Energy Σ T1, impModbuskvarh
Reactive Energy 1st phase T2, impModbuskvarh
Reactive Energy 2nd phase T2, impModbuskvarh
Reactive Energy 3rd phase T2, impModbuskvarh
Reactive Energy Σ T2, impModbuskvarh
Reactive Energy 1st phase T1, expModbuskvarh
Reactive Energy 2nd phase T1, expModbuskvarh
Reactive Energy 3rd phase T1, expModbuskvarh
Reactive Energy Σ T1, expModbuskvarh
Reactive Energy 1st phase T2, expModbuskvarh
Reactive Energy 2nd phase T2, expModbuskvarh
Reactive Energy 3rd phase T2, expModbuskvarh
Reactive Energy Σ T2, expModbuskvarh
Reactive Energy Σ T1, capacitiveModbuskvarh
Reactive Energy Σ T2, capacitiveModbuskvarh
Reactive Energy Σ T1, inductiveModbuskvarh
Reactive Energy Σ T2, inductiveModbuskvarh
L1 phase - reactive powerModbuskvar
L2 Phase - reactive powerModbuskvar
L3 phase - reactive powerModbuskvar
Total reactive powerModbuskvar
Apparent Energy Σ T1ModbuskVAh
Apparent Energy Σ T2ModbuskVAh
L1 phase - apparent powerModbuskVA
L2 Phase - apparent powerModbuskVA
L3 Phase - apparent powerModbuskVA
Total apparent powerModbuskVA
L1 Phase VoltageModbusV
L2 Phase VoltageModbusV
L3 Phase VoltageModbusV
L1 Phase CurrentModbusA
L2 Phase CurrentModbusA
L3 Phase CurrentModbusA
L1 phase - power factorModbus<v.3>
L2 phase - power factorModbus<v.3>
L3 phase - power factorModbus<v.3>
Total power factorModbus<v.3>
FrequencyModbusHz
Total Active EnergyModbus<v.1>
L1 phase - total active energyModbus<v.1>
L2 phase - total active energyModbus<v.1>
L3 phase - total active energyModbus<v.1>

FAQ

No questions have been answered yet.

Ratings and comments

No ratings or comments yet.

Questions and answers

  1. 16-bit registers

    Open

    Hi! I found some bugs in your template. Everywhere where is 32 bit register, 16 bit registers checkbox should be checked. See e.g. total active energy :) Please update the template

    No replies

Report this entry

Report abuse

You have to be logged in to report an entry. Log in