Skip to content
Image of Eastron SDM72D-M
Template

Eastron SDM72D-M

by LoxonautBrand: EastronNo rating yet1,669 downloads

Content languageEnglish

Description

Read values of a Eastron SDM72D-M Energy Meter.

See more information, datasheets, manuals etc. on the vendor's website: https://www.eastroneurope.com/products/view/sdm72modbus

Inputs and outputs · 15

NameTypeUnit
Voltage L1ModbusV
Voltage L2ModbusV
Voltage L3ModbusV
Current L1ModbusA
Current L2ModbusA
Current L3ModbusA
Power L1ModbuskW
Power L2ModbuskW
Power L3ModbuskW
Total active PowerModbuskW
FrequencyModbusHz
Total Energy ImportModbuskWh
Total Energy ExportModbuskWh
Total apparent PowerModbusVA
Total reactive PowerModbusVAr

FAQ

No questions have been answered yet.

Ratings and comments

No ratings or comments yet.

Questions and answers

  1. Template is wrong

    Open

    Just letting you know that the order of registers in the template is wrong

    3 replies

    1. Thanks for the hint. For which registers exactly is the order incorrect so that I can correct it?

    2. For all of them The 'order of registers' flag has to be selected and is not in the template. Since all sensors are combined by 2 registers (32 bit composed by 2 16 bit registers), it has impact on every sensor.

      Just setting the flag resolves the issue.

    3. I also tested the template with an Eastron meter, and it worked for me just as it is currently in the library. However, I'd be happy to take a closer look together to identify the issue if it's not working for you so.

Report this entry

Report abuse