Eastron SDM630-TCP

by Jan WachsmuthBrand: EastronNo rating yet525 downloads

Content languageEnglish

Description

Overview This comprehensive template helps you to read and modify any parameter of an Eastron SDM630-TCP energy meter. This meter supports Modbus/TCP, so it can communicate directly with a Loxone miniserver without any additional hardware.

Hardware setup In the meter DHCP is turned off by default, so you either need to turn on DHCP or configure a fixed IP address. More information can be found in the settings section of the manual, see below. You may also need to adjust the internal modbus communication speed to 57.600 baud. The menu can be found at the end of the settings, but is not included in the manual yet. It is called Set CoState and needs to be set to 0 / 5760.

Using the template The template includes all parameters that are available in the meter, however you should only include the parameters that you need in your Loxone config to avoid unnecessary communication overhead. All parameters have an index number included that matches the one in the manual. So it is easy to find the right parameter e.g. in screenshots. Parameters with watt (W) are converted to kilowatt (kW) in the template. This is done by using the build-in correction option in the Loxone config that are available for each parameter (e.g. 1000 is converted to 1).

Example configuration

The example shows how to connect a simple (unidirectional) meter in Loxone config:

Bidirectional example The next example shows how to connect a bidirectional meter with demand and delivery.

Inputs and outputs · 111

NameTypeUnit
001 - Line voltage L1ModbusV
002 - Line voltage L2ModbusV
003 - Line voltage L3ModbusV
004 - Current L1ModbusA
005 - Current L2ModbusA
006 - Current L3ModbusA
007 - Power L1ModbuskW
008 - Power L2ModbuskW
009 - Power L3ModbuskW
027 - Total system powerModbuskW
036 - Frequency of supply voltagesModbusHz
037 - Energy import since last resetModbuskWh
038 - Energy export since last resetModbuskWh
029 - Total system volt ampsModbusVA
031 - Total system VArModbusVAr
404 - System typeModbus<v>
010 - Volt amps L1ModbusVA
011 - Volt amps L2ModbusVA
012 - Volt amps L3ModbusVA
013 - Volt amps reactive L1ModbusVAr
014 - Volt amps reactive L2ModbusVAr
015 - Volt amps reactive L3ModbusVAr
016 - Power factor L1Modbus<v.3>
017 - Power factor L2Modbus<v.3>
018 - Power factor L3Modbus<v.3>
019 - Phase angle L1Modbus°
020 - Phase angle L2Modbus°
021 - Phase angle L3Modbus°
022 - Average line voltageModbusV
024 - Average line currentModbusA
025 - Sum of line currentsModbusA
032 - Total system power factorModbus<v.1>
034 - Total system phase angleModbus°
039 - Import VArh since last resetModbuskVArh
040 - Export VArh since last resetModbuskVArh
042 - Ah since last resetModbusAh
043 - Total system power demandModbuskW
044 - Maximum total system power demandModbuskW
051 - Total system VA demandModbusVA
052 - Maximum total system power demandModbusVA
053 - Neutral current demandModbusA
054 - Maximum neutral current demandModbusA
101 - L1 to L2 voltageModbusV
102 - L1 to L2 voltageModbusV
103 - L3 to L1 voltageModbusV
104 - Average line to line voltageModbusV
113 - Neutral currentModbusA
118 - L1 voltage THDModbus%
119 - L1 voltage THDModbus%
120 - L3 voltage THDModbus%
121 - L1 current THDModbus%
122 - L2 current THDModbus%
123 - L3 current THDModbus%
125 - Average line voltage THDModbus%
126 - Average line current THDModbus%
128 - Total system power factorModbus<v.3>
130 - L1 current demandModbusA
131 - L2 current demandModbusA
132 - L3 current demandModbusA
133 - Maximum L1 current demandModbusA
134 - Maximum L2 current demandModbusA
135 - Maximum L3 current demandModbusA
168 - L1 to L2 voltage THDModbus%
169 - L2 to L3 voltage THDModbus%
170 - L3 to L1 voltage THDModbus%
171 - Average line to line voltage THDModbus%
172 - Total kWhModbuskWh
173 - Total kVArhModbuskVArh
174 - L1 import kWhModbuskWh
175 - L2 import kWhModbuskWh
176 - L3 import kWhModbuskWh
177 - L1 export kWhModbuskWh
178 - L2 export kWhModbuskWh
179 - L3 export kWhModbuskWh
180 - L1 total kWhModbuskWh
181 - L2 total kWhModbuskWh
182 - L3 total kWhModbuskWh
183 - L1 import kVArhModbuskVArh
184 - L2 import kVArhModbuskVArh
185 - L3 import kVArhModbuskVArh
186 - L1 export kVArhModbuskVArh
187 - L2 export kVArhModbuskVArh
188 - L3 export kVArhModbuskVArh
189 - L1 total kVArhModbuskVArh
190 - L2 total kVArhModbuskVArh
191 - L3 total kVArhModbuskVArh
401 - Demand periodModbusmin
402 - System voltageModbusV
403 - System currentModbusA
405 - KPPAModbus<v>
406 - Network nodeModbus<v>
407 - PasswordModbus<v>
408 - System powerModbuskW
409 - Backlit timeModbusmin
410 - IP addressModbus<v>
414 - DHCP enabledModbus<v>
411 - IP subnet maskModbus<v>
412 - IP default gatewayModbus<v>
413 - IP portModbus<v>
041 - VAh since lst resetModbuskVAh
414 - Enable/Disable DHCPModbus<v>
401 - Demand periodModbusmin
404 - System typeModbus<v>
405 - KPPAModbus<v>
406 - Network nodeModbus<v>
407 - PasswordModbus<v>
409 - Backlit timeModbusmin
410 - IP addressModbus<v>
411 - IP subnet maskModbus<v>
412 - IP default gatewayModbus<v>
413 - IP portModbus<v>