Eastron SDM120M

by PAWEL URBANBrand: Eastron3 (1)1,587 downloads

Content languageEnglish

Description

Modbus RTU template of the energy meter Eastron SDM120M

Inputs and outputs · 21

NameTypeUnit
VoltageModbusV
CurrentModbusA
PowerModbusW
Max. current demandModbusA
Apparent powerModbusVA
Reactive powerModbusVAr
Power FactorModbus<v.2>
FrequencyModbusHz
Energy ConsumptionModbuskWh
Total active energyModbuskWh
Total reactive energyModbuskvar
Energy ProductionModbuskWh
Energy Consumption ReactiveModbuskvarch
Energy Production ReactiveModbuskvarch
Total system power demandModbusW
Max. system power demandModbusW
Import system power demandModbusW
Max. import system power demandModbusW
Export system power demandModbusW
Export system power demandModbusW
Max. export system power demandModbusW

FAQ

No questions have been answered yet.

Ratings and comments

  1. Rated 3 of 5

    Status/Vorgabewert der Registerreihnfolge ist nicht korrekt gesetzt. Möglicherweise ist ein neue Software auf dem Messgerät, die die Reihnfolge der Bytes ändert.

Questions and answers

  1. No Returned values?

    Open

    I’ve used the template for the SEM120M energy meters, I have 5 meters installed and can’t get a returned value on any.

    I have changed the address / ID on the units to 5 different as follows,

    011,012,013,014,015

    I have then changed the modbus address to the corresponding number in loxone config.

    I have left the baud rates at 2400

    I have also left parity as none.

    I have other modbus devices on the bus that are working and returning values but not the meters.

    Can you offer any advice. TIA

    1 reply

    1. Probiere mal in den Einstellungen des Sensors in der Config: --> Registerreihnfolge = false

      Standarteinstellungen am Messgerät = alles unverändert gelassen Speed = 9600 baud parity = none Stoppbit = 2 Kabellänge Modbus = 0,5 m

  2. Keine Werte

    Open

    Leider liefert der Zähler keine Werte über das Modbus Air Gerät

    No replies

  3. "register order" still checked

    Open

    The template delivered no valid values. After I unchecked the "register order" it worked! Then I saw your changelog from 2023, downloaded the template again -> "register order" is checked on all sensors.

    Pls. correct

    No replies