Eastron SDM120M
Content languageEnglish
Description
Modbus RTU template of the energy meter Eastron SDM120M
Inputs and outputs · 21
| Name | Type | Unit |
|---|---|---|
| Voltage | Modbus | V |
| Current | Modbus | A |
| Power | Modbus | W |
| Max. current demand | Modbus | A |
| Apparent power | Modbus | VA |
| Reactive power | Modbus | VAr |
| Power Factor | Modbus | <v.2> |
| Frequency | Modbus | Hz |
| Energy Consumption | Modbus | kWh |
| Total active energy | Modbus | kWh |
| Total reactive energy | Modbus | kvar |
| Energy Production | Modbus | kWh |
| Energy Consumption Reactive | Modbus | kvarch |
| Energy Production Reactive | Modbus | kvarch |
| Total system power demand | Modbus | W |
| Max. system power demand | Modbus | W |
| Import system power demand | Modbus | W |
| Max. import system power demand | Modbus | W |
| Export system power demand | Modbus | W |
| Export system power demand | Modbus | W |
| Max. export system power demand | Modbus | W |
FAQ
No questions have been answered yet.
Questions and answers
No Returned values?
OpenI’ve used the template for the SEM120M energy meters, I have 5 meters installed and can’t get a returned value on any.
I have changed the address / ID on the units to 5 different as follows,
011,012,013,014,015
I have then changed the modbus address to the corresponding number in loxone config.
I have left the baud rates at 2400
I have also left parity as none.
I have other modbus devices on the bus that are working and returning values but not the meters.
Can you offer any advice. TIA
1 reply
Probiere mal in den Einstellungen des Sensors in der Config: --> Registerreihnfolge = false
Standarteinstellungen am Messgerät = alles unverändert gelassen Speed = 9600 baud parity = none Stoppbit = 2 Kabellänge Modbus = 0,5 m
Keine Werte
OpenLeider liefert der Zähler keine Werte über das Modbus Air Gerät
No replies
"register order" still checked
OpenThe template delivered no valid values. After I unchecked the "register order" it worked! Then I saw your changelog from 2023, downloaded the template again -> "register order" is checked on all sensors.
Pls. correct
No replies