Brink Flair
Content languageEnglish
Description
ENG: CO2 sensors ensure optimal ventilation of the home by automatically adjusting the airflow based on the CO2 content. The airflow is determined by the CO2 sensor, which requires the highest level. The CO2 sensor(s) only regulate the unit when the position switch/air control is set to position 1; when the position switch is in position 0 or on the fan symbol (absent) the CO2 control does not operate. Depending on the minimum and maximum (set) PPM values, the CO2 control adjusts the airflow between setting 1 (low setting) and setting 3 (high setting).
1 = Air flow value 2 = Amount of CO2 in the area where the CO2 sensors are located Q Min = Minimum airflow setting 1; for example Flair 325 (Plus) factory setting step 1.2 = 100 m3 /h Q Max = Maximum airflow setting 3; for example Flair 325 (Plus) factory setting step No. 1.4 = 250 m3 /h Min. PPM = Minimum (set) PPM value; for example Flair 325 (Plus) factory setting step no. 6.2 = 400 PPM Max. PPM = Maximum (set) PPM value; for example Flair 325 (Plus) factory setting step No. 6.3 = 1200 PPM
Modbus address: AI reading values : Q Min= 6001 Q Max = 6003 Min. PPM = 6151 Max. PPM = 6152 AQ write values : Q Min= 6001 Q Max = 6003 Min. PPM = 6151 Max. PPM = 6152 For proper functionality, flow control using Co2 LOXONE must be 8000=2, and flow control using 8002. For more details, refer to the modbus UWA2-B/UWA2-E manual.
CZ: CO2 čidla zajišťují optimální ventilaci obydlí díky automatickému nastavení proudění vzduchu na základě CO2 obsahu. Proudění vzduchu určuje CO2 čidlo, které vyžaduje nejvyšší úroveň. CO2 čidlo (čidla) reguluje zařízení, pouze pokud je polohový přepínač/ovládání vzduchu nastaveno v poloze 1; když je polohový přepínač v poloze 0 nebo na symbolu ventilátoru (nepřítomnost) CO2 ovládání nefunguje. V závislosti na minimální a maximální (nastavené) hodnotě PPM regulace CO2 upravuje proudění vzduchu mezi nastavením 1 (nastavení nízké) a nastavením 3 (nastavení vysoké).
1 = Hodnota proudění vzduchu 2 = Množství CO2 v oblasti, kde jsou umístěna CO2 čidla Q Min = Nastavení minimálního proudění vzduchu 1; například Flair 325 (Plus) tovární nastavení krok č. 1.2 = 100 m3 /h Q Max = Nastavení maximálního proudění vzduchu 3; například Flair 325 (Plus) tovární nastavení krok č. 1.4 = 250 m3 /h Min. PPM = Minimální (nastavená) hodnota PPM; například Flair 325 (Plus) tovární nastavení krok č. 6.2 = 400 PPM Max. PPM = Maximální (nastavená) hodnota PPM; například Flair 325 (Plus) tovární nastavení krok č. 6.3 = 1200 PPM
Modbus address: AI čtení hodnot : Q Min= 6001 Q Max = 6003 Min. PPM = 6151 Max. PPM = 6152 AQ zápis hodnot: Q Min= 6001 Q Max = 6003 Min. PPM = 6151 Max. PPM = 6152 Pro správnou funkčnost řízení průtoků pomocí Co2 LOXONE musí být 8000=2, a řízení průtoku pomocí 8002. Více podrobností v návodu modbus UWA2-B/UWA2-E.
Inputs and outputs · 218
| Name | Type | Unit |
|---|---|---|
| Software version number 0 | Modbus | <v.1> |
| Appliance Type | Modbus | <v.1> |
| Dipswitch value | Modbus | <v.1> |
| Serial number 0 | Modbus | <v.1> |
| Serial number 1 | Modbus | <v.1> |
| Serial number 2 | Modbus | <v.1> |
| HRA (Heat Recovery Appliance) Active Function | Modbus | <v.1> |
| Fan control type | Modbus | <v.1> |
| Ventilation mode | Modbus | <v.1> |
| Hardware version | Modbus | <v.1> |
| Software version number 2 | Modbus | <v.1> |
| Temperature sensor exhaust fan | Modbus | °C |
| Software version number 1 | Modbus | <v.1> |
| Current supply pressure | Modbus | Pa |
| Current exhaust pressure | Modbus | Pa |
| Fan Inlet Status | Modbus | <v.1> |
| Setpoint supply air | Modbus | m3/h |
| Current value of supplyair | Modbus | m3/h |
| Speed supply fan | Modbus | RPM |
| Temperature sensorsupply fan | Modbus | °C |
| Fan inlet sensor rel.humidity | Modbus | % |
| Fan exhaust Status | Modbus | <v.1> |
| Setpoint flow exhaust air | Modbus | m3/h |
| current value flowexhaust air | Modbus | m3/h |
| MassFlow exhaust,actual value | Modbus | Kg/h |
| Speed exhaust fan | Modbus | RPM |
| Temperature sensor exhaust fan | Modbus | °C |
| Fan exhaust sensor rel.humidity | Modbus | % |
| Bypass status | Modbus | <v.1> |
| Status preheater | Modbus | <v.1> |
| Capacity of preheater | Modbus | % |
| Frost status | Modbus | <v.1> |
| Frost heaterpower | Modbus | % |
| Flow switch position | Modbus | <v.1> |
| NTC1 temperature | Modbus | °C |
| NTC2 temperature | Modbus | °C |
| RHT Sensor Humidity | Modbus | % |
| Signal output Status | Modbus | <v.1> |
| Status filter | Modbus | <v.1> |
| eBus power status | Modbus | <v.1> |
| Current time | Modbus | <v.1> |
| Current date | Modbus | <v.1> |
| Operating time | Modbus | <v.1> |
| Filters used in days | Modbus | <v.1> |
| Filters used in m3/h | Modbus | <v.1> |
| Total flow in m3/h | Modbus | <v.1> |
| Geo heat exchangerStatus | Modbus | <v.1> |
| CO2 sensor 1 status | Modbus | <v.1> |
| Value CO2 sensor 1 | Modbus | <v.1> |
| CO2 sensor 2 status | Modbus | <v.1> |
| Value CO2 sensor 2 | Modbus | <v.1> |
| CO2 sensor 3 status | Modbus | <v.1> |
| Value CO2 sensor 3 | Modbus | <v.1> |
| CO2 sensor 4 status | Modbus | <v.1> |
| Value CO2 sensor 4 | Modbus | <v.1> |
| Software version numberUIF Module(e.g. "S1.01.03.0001") | Modbus | <v.1> |
| Software version numberUIF Module(e.g. "S1.01.03.0001") | Modbus | <v.1> |
| Software version numberUIF Module(e.g. "S1.01.03.0001") | Modbus | <v.1> |
| Hardware versionnumber UIF Module (e.g."H1.1") | Modbus | <v.1> |
| Device Type | Modbus | <v.1> |
| Dipswitch value | Modbus | <v.1> |
| Language Data versionUIF Module (e.g."S1.01.03.0001") | Modbus | <v.1> |
| Language Data versionUIF Module (e.g."S1.01.03.0001") | Modbus | <v.1> |
| Language Data versionUIF Module (e.g."S1.01.03.0001") | Modbus | <v.1> |
| Software version nr UIFModule (e.g."S1.01.03.0001") | Modbus | <v.1> |
| Software version nr UIFModule (e.g."S1.01.03.0001") | Modbus | <v.1> |
| Software version nr UIFModule (e.g."S1.01.03.0001") | Modbus | <v.1> |
| Local UIF Switch | Modbus | <v.1> |
| Local Button value | Modbus | <v.1> |
| Software version nExtension ModuleUWA2-E (e.g."S1.01.03.0001") | Modbus | <v.1> |
| Software version nExtension ModuleUWA2-E (e.g."S1.01.03.0001") | Modbus | <v.1> |
| Software version nExtension ModuleUWA2-E (e.g."S1.01.03.0001") | Modbus | <v.1> |
| Hardware version nrExtension ModuleUWA2-E (e.g. "H1.1") | Modbus | <v.1> |
| Device Type | Modbus | <v.1> |
| Temperature NTC Extension | Modbus | °C |
| Extension contact 1 | Modbus | <v.1> |
| Extension contact 2 | Modbus | <v.1> |
| Extension AnalogueInput 1 | Modbus | V |
| Extension AnalogueInput 2 | Modbus | V |
| Extension Relay output 1 | Modbus | <v.1> |
| Dipswitch value | Modbus | <v.1> |
| Extension Relay output 2 | Modbus | <v.1> |
| Extension Analogue Output 1 | Modbus | V |
| Extension Analogue Output 2 | Modbus | V |
| Flow preset 0 | Modbus | <v.1> |
| Flow preset 1 | Modbus | <v.1> |
| Flow preset 2 | Modbus | <v.1> |
| Flow preset 3 | Modbus | <v.1> |
| Switch default position | Modbus | <v.1> |
| Use display as switch | Modbus | <v.1> |
| Imbalans allowed | Modbus | <v.1> |
| Imbalance value | Modbus | <v.1> |
| Offset imbalance supply | Modbus | % |
| Offset imbalance exhaust | Modbus | % |
| Bypass mode | Modbus | <v.1> |
| Bypass temperature fromdwelling | Modbus | °C |
| Bypass temperature from outside | Modbus | °C |
| Bypass temperature hysteresis | Modbus | °C |
| Bypass boost | Modbus | <v.1> |
| Bypass boost switch position | Modbus | <v.1> |
| Frost control minimum inlet temperature | Modbus | °C |
| Days before filter warning | Modbus | <v.1> |
| External heater mode | Modbus | <v.1> |
| Postheater setpoint | Modbus | °C |
| RHT (humidity) sensor mode | Modbus | <v.1> |
| RHT (humidity) sensor sensitivity | Modbus | <v.1> |
| CO2 sensor mode | Modbus | <v.1> |
| CO2 sensor 1 low level | Modbus | <v.1> |
| CO2 sensor 1 high level | Modbus | <v.1> |
| CO2 sensor 2 low level | Modbus | <v.1> |
| CO2 sensor 4 high level | Modbus | <v.1> |
| CO2 sensor 2 high level | Modbus | <v.1> |
| CO2 sensor 3 low level | Modbus | <v.1> |
| CO2 sensor 3 high level | Modbus | <v.1> |
| CO2 sensor 4 low level | Modbus | <v.1> |
| Signal output Setting | Modbus | <v.1> |
| Switch type Input 1 | Modbus | <v.1> |
| Digital Input 1 function | Modbus | <v.1> |
| Digital input 1 supply fan function | Modbus | <v.1> |
| Digital Input 1 exhaust fan function | Modbus | <v.1> |
| Switch type Input 2 | Modbus | <v.1> |
| Digital input 2 function | Modbus | <v.1> |
| Digital input 2 supply fan function | Modbus | <v.1> |
| Digital input 2 exhaust fan function | Modbus | <v.1> |
| Analogue input 2 Mode | Modbus | <v.1> |
| Analogue Input 1 Mode | Modbus | <v.1> |
| Analogue input 1 Vmin | Modbus | V |
| Analogue input 1 Vmax | Modbus | V |
| Analogue input 2 Vmin | Modbus | V |
| Analogue input 2 Vmax | Modbus | V |
| Geo-heat exchanger | Modbus | <v.1> |
| Minimum temperature geo-heat exchanger | Modbus | °C |
| Maximum temperaturegeo-heat exchanger | Modbus | °C |
| Default geo heatexchanger Valve Position | Modbus | <v.1> |
| Geo heat exchangervalve output | Modbus | <v.1> |
| Language | Modbus | <v.1> |
| Date format | Modbus | <v.1> |
| Time notation | Modbus | <v.1> |
| Date Month Day | Modbus | <v.1> |
| Date Year | Modbus | <v.1> |
| Time | Modbus | <v.1> |
| DateTime Rest | Modbus | <v.1> |
| Modbus interface type | Modbus | <v.1> |
| Modbus slave address | Modbus | <v.1> |
| Modbus speed | Modbus | <v.1> |
| Modbus control switched on | Modbus | <v.1> |
| Request change in switch position | Modbus | <v.1> |
| Desired flow rate setting | Modbus | <v.1> |
| Request Standby | Modbus | <v.1> |
| Reset filter warning | Modbus | <v.1> |
| Appliance reset | Modbus | <v.1> |
| Flow preset 0 | Modbus | <v.1> |
| Flow preset 1 | Modbus | <v.1> |
| Flow preset 2 | Modbus | <v.1> |
| Flow preset 3 | Modbus | <v.1> |
| Switch default position | Modbus | <v.1> |
| Use display as switch | Modbus | <v.1> |
| Imbalans allowed | Modbus | <v.1> |
| Imbalance value | Modbus | <v.1> |
| Offset imbalance supply | Modbus | % |
| Offset imbalance exhaust | Modbus | % |
| Bypass temperature from dwelling | Modbus | °C |
| Bypass temperature fromoutside | Modbus | °C |
| Bypass temperaturehysteresis | Modbus | °C |
| Bypass boost | Modbus | <v.1> |
| Bypass boost switchposition | Modbus | <v.1> |
| Frost control minimum inlet temperature | Modbus | °C |
| Days before filterwarning | Modbus | <v.1> |
| External heater mode | Modbus | <v.1> |
| Postheater setpoint | Modbus | °C |
| RHT (humidity) sensormode | Modbus | <v.1> |
| RHT (humidity) sensor sensitivity | Modbus | <v.1> |
| CO2 sensor mode | Modbus | <v.1> |
| CO2 sensor 1 low level | Modbus | <v.1> |
| CO2 sensor 1 high level | Modbus | <v.1> |
| CO2 sensor 2 low level | Modbus | <v.1> |
| CO2 sensor 2 high level | Modbus | <v.1> |
| CO2 sensor 3 low level | Modbus | <v.1> |
| CO2 sensor 3 high level | Modbus | <v.1> |
| CO2 sensor 4 low level | Modbus | <v.1> |
| CO2 sensor 4 high level | Modbus | <v.1> |
| Signal output | Modbus | <v.1> |
| Switch type Input 1 | Modbus | <v.1> |
| Digital Input 1 function | Modbus | <v.1> |
| Digital input 1 supply fan function | Modbus | <v.1> |
| Bypass mode | Modbus | <v.1> |
| Digital Input 1 exhaust | Modbus | <v.1> |
| Switch type Input 2 | Modbus | <v.1> |
| Digital input 2 function | Modbus | <v.1> |
| Digital input 2 supply fan function | Modbus | <v.1> |
| Digital input 2 exhaust fan function | Modbus | <v.1> |
| Analogue Input 1 Mode | Modbus | <v.1> |
| Analogue input 1 Vmin | Modbus | V |
| Analogue input 1 Vmax | Modbus | V |
| Analogue input 2 Mode | Modbus | <v.1> |
| Analogue input 2 Vmin | Modbus | V |
| Analogue input 2 Vmax | Modbus | V |
| Geo-heat exchanger | Modbus | <v.1> |
| Minimum temperature geo-heat exchanger | Modbus | °C |
| Maximum temperature geo-heat exchanger | Modbus | °C |
| Default geo heat exchanger Valve Position | Modbus | <v.1> |
| Geo heat exchanger valve output | Modbus | <v.1> |
| Language | Modbus | <v.1> |
| Date format | Modbus | <v.1> |
| Time notation | Modbus | <v.1> |
| Date Month Day | Modbus | <v.1> |
| Date Year | Modbus | <v.1> |
| Time | Modbus | <v.1> |
| DateTime Rest | Modbus | <v.1> |
| Modbus interface type | Modbus | <v.1> |
| Modbus slave address | Modbus | <v.1> |
| Modbus speed | Modbus | <v.1> |
| Modbus control switched on | Modbus | <v.1> |
| Request changein switch position | Modbus | <v.1> |
| Desired flow rate setting | Modbus | <v.1> |
| Request Standby | Modbus | <v.1> |
| Reset filter warning | Modbus | <v.1> |
| Appliance reset | Modbus | <v.1> |