Belimo Energy Valve V3 Modbus TCP

by BELIMO AutomationNo rating yet994 downloads

Content languageEnglish

Description

The Belimo Energy Valve™ offers energy metering, pressure-independent control and delta T management in one device.


What is the difference between Energy Valve V3 & Energy Valve V4?

- The Energy Valve V3 does not have an MID-certified energy meter. - The Energy Valve V3 has no Power over Ethernet (PoE)


Structure:


The choice of paring Belimo Energy Valve with Loxone offers the possibility of:

- [Demand based Heating and Cooling]: The Energy Valve regulates depending on the Room Heating or Cooling requirement, Heating Curve, Presence detection, Window status, Automatic Shading, Weather Forecast and Energy Management (PV Surplus, Variable Electricity Tariffs, Load Management). - [Flow/Power/Energy Monitoring and Analysis]: The integrated Water Flow / Power / Heating & Cooling consumption recording of the Energy Valve ensures transparent Energy Flow Monitoring with individually created System Schematics. Using the Energy Flow Monitor for thermal outputs provides an overview of total and current energies. Energy leaks in the building can be found quickly. The valves that do not close tightly or, for example, consumers that are in “manual mode” are discovered. Using and storing statistics, creating individual notifications. e.g. threshold value excesses or error notifications. - [Automatic Hydraulic Balancing]: In the central heating & cooling system or in the lines to the consumers under all operating conditions (full load and partial load). Heating and cooling loads can be optimally supplied thanks to the simple and demand-based control. Thanks to the delta-T Optimization function of the Energy Valve, water volume flows can be reduced to the minimum and Pump Energy can therefore be saved. By using an Energy Valve, pumps can be made smaller, balancing valves, control drives and heat meters can be replaced by a product, the Energy Valve! This reduces the project costs. Differential pressure fluctuations in the network are compensated electronically. - [Application in a hybrid system]: The possibility of application in a Hybrid system or in a system that uses different Energy sources ensures cost independence, a high level of comfort and flexibility in heating and cooling. Facilitates the combination of complex Hydraulics such as multiple base-load heat generators (e.g. Heatpump or Biomass) with Peak-Load Heat Sources (e.g. Oil or Gas). - [Continuous Glycol monitoring]: Manual measurements are replaced. If the amount of Glycol is too low, there is a risk of freezing or water damage. If the proportion is too high, the energy consumption of the circulation pump increases. The Glycol concentration can be tracked in the statistics, individual thresholds can be set for notifications or automatic dosing can be carried out. - [Dewpoint monitoring]: With the more accurate and responsive Flow sensor of the Belimo Energy Valve™, systems can detect and shut off water flows before condensate forms on the chilled beams. The minimum flow temperature can be calculated using a formula building block and controlled with the EPIV valve based on the room temperatures and room humidity. - [Cost Saving]: Fast commissioning via Belimo Assistant and fast error finding thanks to Belimo and Loxone Diagnose Tools.

Inputs and outputs · 56

NameTypeUnit
Actuator typeModbus<v>
Relative positionModbus%
Absolute positionModbus°
Relative flowModbus%
Absolute volumetric flow in selected unitModbusl/min
Setpoint analogModbusV
Temperature 1 in degree CelsiusModbus°C
Temperature 1 in degree FahrenheitModbus°F
Temperature 2 in degree CelsiusModbus°C
Temperature 2 in degree FahrenheitModbus°F
Delta temperature in KModbusK
Delta temperature in degree FModbus°F
Glycol concentrationModbus%
Relative powerModbus%
Series Number 1st partModbus<v>
Series Number 2nd partModbus<v>
Series Number 4th partModbus<v>
Firmware versionModbus<v>
Malfunction and Service InformationModbus<v>
DeltaT Manager StatusModbus<v>
Absolute volumetric flow in liter per secondModbusl/s
Absolute volumetric flow in gpmModbusgpm
Setpoint absolute flow in selected unitModbusl/min
Absolute power in selected unitModbuskW
Absolute power in kWModbuskW
Absolute power in kBtu per hourModbuskBtu/h
Energy Cooling in selected unitModbuskWh
Energy Cooling in kWhModbuskWh
Energy Cooling in kBtuModbuskBtu
Energy Heating in selected unitModbuskWh
Energy Heating in kWhModbuskWh
Energy Heating in kBtuModbuskBtu
Nominal volumetric flow in selected unitModbusl/min
Nominal volumetric flow in liter per secondModbusl/s
Nominal volumetric flow in gpmModbusgpm
Nominal power in selected unitModbus<v.3>
Nominal power in kWModbuskW
Nominal power in kBtu per hourModbuskBtu/h
Setpoint flow at DeltaT in liter per secondModbusl/s
Setpoint flow at DeltaT in gpmModbusgpm
SetpointModbus%
Override controlModbus<v>
Vmax in percent of VnomModbus%
Pmax in percent of PnomModbus%
Delta T LimitationModbus<v>
Setpoint DeltaT in KModbusK
Setpoint DeltaT in FModbus°F
Control ModeModbus<v>
Unit Selection FlowModbus<v>
Unit Selection PowerModbus<v>
Unit Selection EnergyModbus<v>
Setpoint SourceModbus<v>
Absolute Vmax in liter per secondModbusl/s
Absolute Vmax in gpmModbusgpm
Absolute Pmax in kWModbuskW
Absolute Pmax in kBtu per hourModbuskBtu/h

FAQ

No questions have been answered yet.

Ratings and comments

No ratings or comments yet.

Questions and answers

  1. Fehlerhafte Register

    Open

    Guten Tag.

    Habe diese Woche 5 Belimo Energy Valve in Betrieb genommen. Jedoch musst ich das komplete Register überarbeiten. Abgesehen vom Setpoint stimmt da praktisch nichts mehr.

    Mit freundlichen Grüssen Zumstein Mathias

    No replies

Report this entry

Report abuse

You have to be logged in to report an entry. Log in